13
English (US)
6.3 User interface (AUTO version)
Eight settings are easily available by pushing
the button. Three LEDs show the chosen
setting.
The user interface allows selection between
eight control curves in two control modes:
•
three proportional pressure curves (PP) + PP
AUTOAdapt
•
three constant pressure curves (CP) + CP
AUTOAdapt.
First startup is in factory presetting of
proportional pressure curve 2.
If a setting has already been selected: Start at
the actual setting.
•
Press the button for two seconds.
– The pump enters setting mode, and the
LED starts flashing.
•
Each time you press the button, the setting
changes.
– LEDs 1, 2 and 3 are permanently on, and
control curve and mode change.
– Flashing mode:
Fast: proportional pressure
Slow: constant pressure/power.
•
If the button is not pressed for ten seconds,
the selected setting is adapted, and the
pump returns to operating mode.
•
LED 1, 2 or 3 is permanently on, or all are
permanently on:
The pump is running with the selected
control curve and mode.
Fig. 7