background image

English (GB)

17

Using p

min

 and Q

max

, the minimum diaphragm tank size, precharge pressure and pressure switch settings 

can be found in the guideline table below: 

Example

p

min

 = 35 m head, Q

max

 = 2.5 m

3

/h. 

On the basis of this information, the following values can be found in the table: 

Minimum diaphragm tank size = 33 litres. 

p

pre

= 31.5 m head. 

p

cut-in

= 36 m head. 

p

cut-out

= 50 m head.

1 m head = 0.098 bar.

8.3 Built-in protection

The motor incorporates an electronic unit which 
protects the motor in various situations.

In case of overload, the built-in overload protection 
will stop the pump for 5 minutes. After that period, 
the pump will attempt to restart. 

If the pump has been stopped as a result of dry 
running, it will start automatically after 5 minutes.

If the pump is restarted and the borehole is empty, 
the pump will stop after 30 seconds.

Resetting of the pump: Switch off the power supply 
for 1 minute. 

The motor is protected in case of:

dry running

voltage surges (up to 6000 V)
In areas with high lightning intensity, external 
lightning protection is required.

overvoltage

undervoltage

overload 

overtemperature.

SQE pumps/MSE 3 motors

9. Maintenance and service

The pumps are normally maintenance-free.

Deposits and wear may occur. For that purpose, 
service kits and service tools are available from 
Grundfos. The Grundfos Service Manual is available 
on request.

The pumps can be serviced at a Grundfos service 
centre.

9.1 Contaminated pumps

If Grundfos is requested to service the pump, 
Grundfos must be contacted with details about the 
pumped liquid, etc. before the pump is returned for 
service. Otherwise Grundfos can refuse to accept 
the pump for service.

However, any application for service (no matter to 
whom it may be made) must include details about 
the pumped liquid if the pump has been used for 
liquids which are injurious to health or toxic. 

p

min

[m]

Q

max

 [m

3

/h]

p

pre

[m]

p

cut-in

[m]

p

cut-out

[m]

0.6 0.8

1

1.2 1.5

2

2.5

3

3.5

4

4.5

5

5.5

6

6.5

7

7.5

8

Diaphragm tank size [litres]

25

8

8

18

18 18 18 24 33 33 50 50 50 50 80 80 80 80 80

22.5

26

40

30

8

8

18

18 18 24 33 33 50 50 50 50 80 80 80 80 80

27

31

45

35

8

18

18

18 18 24 33 33 50 50 50 80 80 80 80 80

31.5

36

50

40

8

18

18

18 18 24 33 50 50 50 80 80 80 80 80

36

41

55

45

8

18

18

18 24 33 33 50 50 50 80 80 80 80

40.5

46

60

50

8

18

18

18 24 33 50 50 50 80 80 80 80

45

51

65

55

18 18

18

18 24 33 50 50 50 80 80 80

49.5

56

70

60

18 18

18

18 24 33 50 50 80 80 80 80

54

61

75

65

18 18

18

24 24 33 50 50 80 80 80 80

58.5

66

80

Note

Via the CU 300 or CU 301, the dry-
running stop limit of the MSE 3 motors 
can be adjusted to match the actual 
application.

Note

If a pump has been used for a liquid 
which is injurious to health or toxic, 
the pump will be classified as 
contaminated.

Содержание SQE-NE Series

Страница 1: ...on 12 6 1 General 12 6 2 Assembly of pump part and motor 12 6 3 Removal of non return valve 12 6 4 Fitting the cable plug to the motor 13 6 5 Fitting the cable guard 13 6 6 Cable sizing 14 6 7 Fitting...

Страница 2: ...ator As a minimum the generator output must be equal to the motor P1 kW 10 Starting current The motor starting current is equal to the highest value stated on the motor nameplate Power factor PF 1 Mot...

Страница 3: ...ng a screwdriver or a similar tool 4 Inject motor liquid into the motor with a filling syringe or the like 5 To allow possible air to escape move the motor from side to side 6 Refit the filling plug a...

Страница 4: ...arked with the following symbol Supply voltage 1 x 200 240 V 10 6 50 60 Hz PE The current consumption can only be measured by means of a true RMS instrument If other instruments are used the value mea...

Страница 5: ...be used on the clamping faces of the pump part See fig 6 Fig 6 When pump part and motor have been assembled correctly there must not be a clearance between pump part and motor 6 3 Removal of non retur...

Страница 6: ...earance between the motor and the cable plug 6 5 Fitting the cable guard To fit the cable guard proceed as follows 1 Make sure that the submersible drop cable lies flat in the cable guard 2 Place the...

Страница 7: ...Fitting the submersible drop cable It is recommended to join the submersible drop cable and the motor cable by means of a Grundfos cable termination kit type KM For larger cross sections please contac...

Страница 8: ...lation depths Maximum installation depth below the static water level 150 metres See fig 11 Minimum installation depths below the dynamic water level Vertical installation During start up and operatio...

Страница 9: ...switch and diaphragm tank during starting will be lower than the pump cut in pressure set on the pressure switch pcut in This lower pressure is called minimum pressure pmin pmin is equal to the desir...

Страница 10: ...ce tools are available from Grundfos The Grundfos Service Manual is available on request The pumps can be serviced at a Grundfos service centre 9 1 Contaminated pumps If Grundfos is requested to servi...

Страница 11: ...n the electric installation are blown Replace the blown fuses If the new ones blow too the electric installation and the submersible drop cable should be checked b The ELCB or the voltage operated ELC...

Страница 12: ...e is defective Replace the riser pipe i Undervoltage has occurred Check the power supply 4 Frequent starts and stops a The differential of the pressure switch between the start and stop pressures is t...

Страница 13: ...d neutral Connect the voltmeter to the terminals at the connection The voltage should when the motor is loaded be within the range specified in section 5 Electrical connection Large variations in supp...

Отзывы: