background image

English (GB)

5

8. Fault finding the product

DANGER

Electric shock

Death or serious personal injury
- Before removing the terminal box cover and before 

removal or dismantling the product, make sure that 
the power supply has been switched off and that it 
cannot be accidentally switched on.

Fault

Cause

Remedy

1. The motor does not 

run when started.

a) Power supply failure.

Reestablish normal power supply.

b) The thermal protection device of the motor has 

tripped.

Wait until the motor cools down to allowable 
temperature. The motor then restarts.
If the motor still cannot start, contact Grundfos.

c) The product has not been in use for a long 

time.

Switch off the power supply and rotate the motor 
non-drive end shaft.

d) The motor is defective.

Repair the motor.

2. The product is leaking. a) There is a leakage in the gasket.

Replace the gasket.

b) There is a leakage in the shaft seal.

Replace the shaft seal.

3. The pump capacity is 

not constant.

a) The pump inlet pressure is too low.

Increase the liquid level on the inlet side.
Open the isolating valve in the inlet pipe.

b) The inlet pipe or product is partly blocked by 

impurities.

Clean the pipeline or product.

c) The product draws in air.

Release the air in the pipeline and product.

4. The product runs but 

does not deliver the 
rated flow.

a) The inlet pipe or product is blocked by 

impurities.

Clean the pipeline or product.

b) The non-return valve is blocked in closed 

position.

Clean and open the non-return valve.

c) The direction of rotation is wrong.

Interchange two phases of power supply.

d) There is a leakage in the inlet pipe.

Repair or replace the pipeline.

e) There is air in the inlet pipe or product.

Check the gasket in the pipe connection, make sure 
the gasket works.

5. The motor protection 

triggers frequently.

a) The power supply is not stable.

Make sure the power supply is stable.

b) The impeller is stuck.

Find the root cause, then repair.

c) The ambient temperature is too high.

Make sure the ambient temperature is within the 
normal range: maximum 40 °C.

Содержание SPRING N Series

Страница 1: ...SPRING N SPRING T 50 Hz Service instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...avoided could result in death or serious personal injury CAUTION Indicates a hazardous situation which if not avoided could result in minor or moderate personal injury SIGNAL WORD Description of hazar...

Страница 3: ...6 8953 1417 Pos Designation Quantity Dimensions Torque Nm 67 Nut 1 M6 5 0 5 M8 11 1 1 25a Stud 2 1 M6 2 0 2 18 Screw 0 1 M10 8 0 8 28 Screw 4 M8 15 1 5 A B C D E F G H I J Tool Designation For pos Fur...

Страница 4: ...seal face with your fingers 3 Press the stationary shaft seal part home using a punch of soft material 4 Spray soapy water on the rotating shaft seal part 5 Press the rotating shaft seal part home us...

Страница 5: ...The pump capacity is not constant a The pump inlet pressure is too low Increase the liquid level on the inlet side Open the isolating valve in the inlet pipe b The inlet pipe or product is partly blo...

Страница 6: ...English GB 6 9 Exploded views Fig 4 Exploded view SPRING T TM06 9572 3817 105 6 172 156b 151 156 72a 109 440a 441b 38b 25a 300 38b 25a 440a 441b 28 49 67 28a 66a...

Страница 7: ...English GB 7 Fig 5 Exploded view SPRING N TM06 9573 3817 156b 105 49 6 172 18 38 25a 38b 109 156 151 300 72a 28 67...

Страница 8: ...8...

Страница 9: ...8 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznes...

Страница 10: ...3889 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: