background image

English (US)

6

6.1.9 Connections

As a precaution, the wires to be connected to the following 
connection groups must be separated from each other by 
reinforced insulation in their entire lengths: 

Group 1: Inputs

• start/stop

terminals 2 and 3

• digital input

terminals 1 and 9

• setpoint input

terminals 4, 5 and 6

• sensor input

terminals 7 and 8

• GENIbus

terminals B, Y and A

All inputs (group 1) are internally separated from the power-
conducting parts by reinforced insulation and galvanically 
separated from other circuits.
All control terminals are supplied with protective extra-low voltage 
(PELV), thus ensuring protection against electric shock.

Group 2: Output (relay signal, terminals NC, C, NO)

The output (group 2) is galvanically separated from other circuits. 
Therefore, the supply voltage or protective extra-low voltage can 
be connected to the output as desired.

Group 3: Power supply (terminals N, PE, L)

Fig. 4

Connection terminals

A galvanic separation must fulfill the requirements for reinforced 
insulation including creepage distances and clearances specified 
in EN 60335.

6.2 Three-phase pumps, 1 - 10 Hp

6.2.1 Preparation

Before connecting the E-pump to the power supply, take the 
issues illustrated in the figure below into consideration.

Fig. 5

Power supply-connected pump with power switch, 
backup fuses, additional protection and protective 
grounding

6.2.2 Protection against electric shock - indirect contact

EN 50178 and BS 7671 specify the following precautions when 
leakage current > 3.5 mA: 
• The pump must be stationary and installed permanently.
• The pump must be permanently connected to the power

supply.

• The grounding connection must be carried out as duplicate

leads.

Protective ground leads must always have a yellow/green (PE) or 
yellow/green/blue (PEN) color marking. 

6.2.3 Backup fuses 

For recommended fuse sizes, see section 

22.1 Supply voltage

 on 

page 33.

6.2.4 Additional protection

If the pump is connected to an electric installation where an 
ground leakage circuit breaker (ELCB) is used as additional 
protection, the circuit breaker must be of a type marked with the 
following symbols:

1RWH

1RWH

If no external on/off switch is connected, connect 
terminals 2 and 3 using a short wire.

T

M

02

 07

95

 09

04

0/1

10K

RUN

STOP

NC C NO

N PE L

1 9 8 7

6 5 4 3 2

B Y A

0-10 V

0/4-20 mA

4-20 mA

0/4-20 mA

0-10 V

1: Digital input 
9: GND (frame)
8: +24 V
7: Sensor input
B: RS-485B
Y: Screen
A: RS-485A

6: GND (frame) 
5: +10 V
4: Setpoint input
3: GND (frame)
2: Start/stop

Group 1

Group 3

Group 2

Warning

The user or the installer is responsible for the 
installation of correct grounding and protection 
according to current national and local 
standards. All operations must be carried out by 
qualified personnel.

Warning

Never make any connections in the pump 
terminal box unless all electric supply circuits 
have been switched off for at least 5 minutes.

Note for instance that the signal relay may be 
connected to an external supply which is still 
connected when the power supply is 
disconnected.

The above warning is indicated on the motor terminal 
box by this yellow label: 

T

M

00

 92

70

 46

96

Warning

The pump must be grounded in accordance with 
national regulations.

As the leakage current of 5 - 10 Hp (4 - 7.5 kW) 
motors is > 3.5 mA, take extra precautions when 
grounding these motors.

L1

L2

L3

L2

L1

L3

PE

ELCB

ELCB

DBP-1 - GRUNDFOS PUMP CRE - 99392005

Содержание SPKE Series

Страница 1: ...GRUNDFOS INSTRUCTIONS CRE CRIE CRNE CRKE SPKE MTRE CHIE CME 1 3 phase Installation and operating instructions DBP 1 GRUNDFOS PUMP CRE 99392005...

Страница 2: ...2...

Страница 3: ...the exclusion or limitation of incidental or consequential damages and some jurisdictions do not allow limit actions on how long implied warranties may last Therefore the above limitations or exclusio...

Страница 4: ...an be read via the R100 If special or customized settings are required use the Grundfos PC Tool E products Contact your local Grundfos company for more information 5 Mechanical installation The pump m...

Страница 5: ...epted from this is the protective ground lead which must be so long that it is the last one to be disconnected in case the cable is inadvertently pulled out of the cable entry Fig 3 Power supply conne...

Страница 6: ...e permanently connected to the power supply The grounding connection must be carried out as duplicate leads Protective ground leads must always have a yellow green PE or yellow green blue PEN color ma...

Страница 7: ...nal start stop when starting stopping the pump When the pump is switched on via an external on off switch it will start immediately Automatic restart However automatic restart only applies to fault ty...

Страница 8: ...clearances specified in EN 60335 TM05 3239 1012 6 GND frame 5 10 V 4 Setpoint input 3 GND frame 2 Start stop Group 1 Group 2 Group 3 1 Digital input 2 9 GND frame 8 24 V 7 Sensor input B RS 485B Y Scr...

Страница 9: ...ection The pump requires no external motor protection The motor incorporates thermal protection against slow overloading and blocking IEC 34 11 TP 211 6 3 6 Protection against voltage transients The p...

Страница 10: ...thus ensuring protection against electric shock Group 2 Output relay signal terminals NC C NO The output group 2 is galvanically separated from other circuits Therefore the supply voltage or protectiv...

Страница 11: ...s short as possible 6 5 E pump electrical connections 6 5 1 Connection of E pump to Danfoss pressure sensor MBS3000 The blue wire of the pressure sensor is connected to the 7 terminal of the E pump Th...

Страница 12: ...top the pump has been stopped Min the pump is operating at its minimum speed Max the pump is operating at its maximum speed Figure 18 is a schematic illustration of min and max curves Fig 18 Min and m...

Страница 13: ...and the green indicator light flashes Setting to Min Press continuously to change to the min curve of the pump bottom light field flashes When the bottom light field is on press for 3 seconds until th...

Страница 14: ...ight During communication the R100 must be pointed at the control panel When the R100 communicates with the pump the red indicator light will flash rapidly Keep pointing the R100 at the control panel...

Страница 15: ...10 3 10 10 2 6 10 3 4 2 10 3 11 1 10 1 4 1 10 2 7 2 10 3 5 10 3 12 10 2 8 2 10 3 6 10 3 13 1 10 2 9 1 10 3 7 10 3 14 1 10 3 7 4 10 3 15 1 1 This display only appears for three phase pumps 1 30 Hp 2 Th...

Страница 16: ...Fault indications In E pumps faults may result in two types of indication alarm or warning An alarm fault will activate an alarm indication in R100 and cause the pump to change operating mode typicall...

Страница 17: ...The tolerance of the displayed value is stated under each display The tolerances are stated as a guide in of the maximum values of the parameters 10 2 1 Actual setpoint This display shows the actual s...

Страница 18: ...motor bearings The controller monitors the operating pattern of the pump and calculates the period between bearing replacements The displayable values are these in 2 years in 1 year in 6 months in 3...

Страница 19: ...he signal types is selected the actual setpoint is influenced by the signal connected to the external setpoint input See section 14 External setpoint signal on page 27 10 3 4 Signal relay Pumps of 0 5...

Страница 20: ...20 Dry running only three phase pumps When this function is selected lack of inlet pressure or water shortage can be detected This requires the use of an accessory such as these a Grundfos Liqtec dry...

Страница 21: ...setpoint Recommended diaphragm tank size If a diaphragm tank of the above size is installed in the system the factory setting of H is the correct setting If the tank installed is too small the pump wi...

Страница 22: ...Installation of the AYB cable 91125604 a Remove the plug from each MLE casing with a flat head screw driver see fig 33 b Thread a new cable gland into each MLE casing with a crescent wrench see fig 33...

Страница 23: ...ndication when the motor bearings are due to be relubricated or replaced See section 10 1 3 Fault indications on page 16 When the motor bearings have been relubricated or replaced confirm this action...

Страница 24: ...2 4 10 3 4 2 10 3 9 1 10 2 5 10 3 4 2 10 3 10 10 2 6 10 3 5 10 3 11 1 10 2 7 2 10 3 6 10 3 12 10 2 8 2 10 3 7 4 10 3 13 1 10 3 14 1 10 3 15 1 1 This display only appears for three phase pumps 1 30 Hp...

Страница 25: ...4 10 3 4 2 10 3 9 1 10 2 5 10 3 4 2 10 3 10 10 2 6 10 3 5 10 3 11 1 10 2 7 2 10 3 6 10 3 12 10 2 8 2 10 3 7 4 10 3 13 1 10 3 14 1 10 3 15 1 1 This display only appears for three phase pumps 1 30 Hp 2...

Страница 26: ...the E pump to operating mode Stop or Max and the external signal can only set the E pump to operating mode Stop 13 External forced control signals The pump has inputs for external signals for these f...

Страница 27: ...ernal setpoint signal in control mode uncontrolled 15 Bus signal The pump supports serial communication via an RS 485 input The communication is carried out according to the Grundfos bus protocol GENI...

Страница 28: ...osition of indicator lights on single phase pumps Fig 42 Position of indicator lights on three phase pumps Besides the pump incorporates an output for a potential free signal via an internal relay For...

Страница 29: ...t Alarm or is running with a Warning or Relubricate indication If the pump was stopped restarting will be attempted it may be necessary to restart the pump by resetting the Fault indication If the cau...

Страница 30: ...ow to switch an E pump from normal operation to emergency operation Use the screws from the power supply terminals and the nuts from the motor terminals 4 Insulate the three leads from each other by m...

Страница 31: ...0 240 V 10 10 50 60 Hz 2 2 PE Cable Max 1 5 mm2 12 AWG Use min 158 F 70 C copper conductors only Recommended fuse size Motor sizes from 0 5 1 5 Hp Max 10 A Standard as well as quick blow or slow blow...

Страница 32: ...1 22 4 Inputs output Start stop External potential free contact Voltage 5 VDC Current 5 mA Screened cable 0 5 1 5 mm2 28 16 AWG Digital External potential free contact Voltage 5 VDC Current 5 mA Scree...

Страница 33: ...er Max load 2 5 mA Short circuit protected 24 V power supply for sensors Max load 40 mA Short circuit protected Signal relay output Potential free changeover contact Maximum contact load 250 VAC 2 A c...

Страница 34: ...of in an environmentally sound way 1 Use the public or private waste collection service 2 If this is not possible contact the nearest Grundfos company or service workshop Motor size Hp Short circuit...

Страница 35: ...ymmetrical amperes must not be less than the values stated in table below USA Hp 25 1 5 Overload protection Degree of overload protection provided internally by the drive in percent of full load curre...

Страница 36: ...Appendix 36 DBP 1 GRUNDFOS PUMP CRE 99392005...

Страница 37: ...913 227 3500 Canada GRUNDFOS Canada Inc 2941 Brighton Road Oakville Ontario L6H 6C9 Phone 1 905 829 9533 Telefax 1 905 829 9512 M xico Bombas GRUNDFOS de M xico S A de C V Boulevard TLC No 15 Parque I...

Отзывы: