The cross-section (q) of the cable should meet the following 
requirements: 

1. The submersible drop cable should be dimensioned to the 

rated maximum current (I) of the motor. 

2. The cross-section should be sufficient to make a voltage drop 

over the cable acceptable. 

Use the largest of the cross sections found under points 1. and 2. 

Re 1: The following table specifies the current value of GRUND-
FOS submersible drop cables (i.e. the maximum current tolerated 
by the drop cable) at an ambient temperature of maximum 30°C. 
Please contact GRUNDFOS if the ambient temperature lies 
above 30°C. 

When sizing the submersible drop cable, make sure that the rated 
maximum current does not exceed the current value (I

s

). 

For star-delta starting, however, size the cables so that 0.58 x the 
rated maximum current of the motor does not exceed the current 
value (I

s

) of the cables. 

If GRUNDFOS submersible drop cables are not used, the cross-
section should be selected on the basis of the current values of 
the actual cables. 

Re 2: 
Note:
 The cross-section of the submersible drop cable must be 
large enough to meet the voltage quality requirements specified 
in section 4.1 General

Determine the voltage drop for the cross-section of the submersi-
ble drop cable by means of the diagrams on pages 110 and 111, 
where

I =

Rated maximum current of the motor.
For star-delta starting 
I = rated maximum current of the motor x 0.58. 

Lx =

Length of cable converted to a voltage drop of 1% of the 
nominal voltage. 

Lx =

q =

Cross-section of submersible drop cable. 

Draw a straight line between the actual I-value and the Lx-value. 
Where the line intersects the q-axis, select the cross-section that 
lies right above the intersection. 

The diagrams are made on the basis of the formula:

L =

where 

L =

Length of submersible drop cable [m]

U =

Nominal voltage [V]

U =

Voltage drop [%]

I =

Rated maximum current of the motor [A]

cos

  = 0.9 

 =

Specific resistance: 0.02 [

mm²/m]

q =

Cross-section of submersible drop cable [mm²]

sin

 = 0.436 

Xl =

Inductive resistance: 0.078 x 10

-3

 [

/m]

4.5 Connection of motor 

Three-phase submersible motors must be protected, see section 
4.2 Motor protection

For electrical connection by means of the CU 3, see the separate 
installation and operating instructions for this unit. 

When a conventional motor starter is being used, the electrical 
connection should be carried out as described below. 

4.5.1 Checking of direction of rotation 

Note: The pump must not be started until the suction intercon-
nector has been completely submerged in the liquid. 

When the pump has been connected to the electricity supply, 
determine the correct direction of rotation as follows: 

1. Start the pump and check the quantity of water and head 

developed. 

2. Stop the pump and interchange two of the phase connections. 

In the case of motors wound for star-delta starting, exchange 
U1 by V1 and U2 by V2. 

3. Start the pump and check the quantity of water and head 

developed. 

4. Stop the pump. 

5. Compare the results taken under points 1. and 3. The connec-

tion which gives the larger quantity of water and the higher 
head is the correct connection. 

4.5.2 GRUNDFOS motors, direct-on-line starting 

The connection of GRUNDFOS submersible motors wound for 
direct-on-line starting appears from the following table and fig. 8. 

Check the direction of rotation as described in section 
4.5.1 Checking of direction of rotation

Fig. 8

4.5.3 GRUNDFOS motors, star-delta starting 

The connection of GRUNDFOS submersible motors wound for 
star-delta starting appears from the following table and fig. 9. 

q [mm²]

I

s

 [A]

q [mm²]

I

s

 [A]

1.5

18

50 153

2.5

25

70 196

4

34

95 238

6

43

120 276

10

60

150

319

16

80

185

364

25 101

240

430

35 126

300

497

Mains 

Cable/connection

GRUNDFOS 6", 8", 10" and 12" motors

L1 U

L2 V

L3  

W

PE  

PE

T

M

00

 13

64

 50

92

Connection

GRUNDFOS 6" motors

U1

Brown

V1

Blue

W1

Black

W2

Brown

U2

Blue

V2

Black

PE

Yellow/green

L2 L3

M

L1

PE

U

V W PE

3

length of drop cable

permissible voltage drop in %

q

U x 

U

I x 1.73 x 100 x (cos



x

+  sin



x Xl)

Содержание SP-G

Страница 1: ...SP G GRUNDFOS INSTRUCTIONS Installation and operating instructions ...

Страница 2: ... 60335 1 2002 e EN 60335 2 41 2003 excepto nos pontos 25 1 e 25 8 Bomba com ponta de veio livre A Grundfos declara sob sua única responsabilidade que os produtos SP G aos quais diz respeito esta declaração estão em conformidade com as seguintes Directivas do Conselho sobre a aproximação das legislações dos Estados Membros da CE Directiva Máquinas 2006 42 CE Norma utilizada EN 809 2009 Antes de col...

Страница 3: ...24 Istruzioni di installazione e funzionamento 34 Instrucciones de instalación y funcionamiento 43 Instruções de instalação e funcionamento 52 Οδηγίες εγκατάστασης και λειτουργίας 62 Installatie en bedieningsinstructies 72 Monterings och driftsinstruktion 82 Asennus ja käyttöohjeet 91 Monterings og driftsinstruktion 100 ...

Страница 4: ...e a month If a motor has been stored for more than one year before installa tion the rotating parts of the motor must be dismantled and checked before use The pump should not be exposed to direct sunlight If the pump has been unpacked it should be stored horizontally adequately supported or vertically to prevent misalignment of the pump Make sure that the pump cannot roll or fall over During stora...

Страница 5: ...ith the filling syringe fig 3 until the liquid runs back out of the filling hole 4 Replace the screw in the filling hole and tighten securely before changing the position of the pump Torque 3 0 Nm The submersible pump is now ready for installation Fig 3 3 1 3 Refilling GRUNDFOS submersible motors MMS 6000 MMS 8000 MMS 10000 and MMS 12000 To refill the motor proceed as follows 1 Position the submer...

Страница 6: ...tor makes See motor specifications 4 Electrical connection 4 1 General The electrical connection should be carried out by an authorized electrician in accordance with local regulations The supply voltage rated maximum current and cos appear from the loose data plate that must be fitted close to the installa tion site The required voltage quality for GRUNDFOS MS submersible motors measured at the m...

Страница 7: ...ter must be protected by means of a motor starter with thermal relay or a CU 3 and contactor s GRUNDFOS MMS motors have no built in temperature transmit ter A Pt100 sensor is available as an accessory Motors with a Pt100 sensor must be protected by means of a motor starter with thermal relay or a CU 3 and contactor s Motors without a Pt100 sensor must be protected by means of a motor starter with ...

Страница 8: ... Specific resistance 0 02 mm m q Cross section of submersible drop cable mm sin 0 436 Xl Inductive resistance 0 078 x 10 3 m 4 5 Connection of motor Three phase submersible motors must be protected see section 4 2 Motor protection For electrical connection by means of the CU 3 see the separate installation and operating instructions for this unit When a conventional motor starter is being used the...

Страница 9: ...ightened diagonally to the torques stated in the following table Note Make sure that the pump chambers are aligned when assembly has been completed 5 2 Fitting of submersible drop cable Before fitting the submersible drop cable to the motor make sure that the cable socket is clean and dry To facilitate the fitting of the cable lubricate the rubber parts of the cable plug with non conducting silico...

Страница 10: ...osed off to approx 1 3 of its maximum volume of water Check the direction of rotation as described in section 4 5 1 Checking of direction of rotation If there are impurities in the water the valve should be opened gradually as the water becomes clearer The pump should not be stopped until the water is completely clean as otherwise the pump parts and the non return valve may choke up As the valve i...

Страница 11: ...d at a GRUNDFOS service centre If GRUNDFOS is requested to service the pump GRUNDFOS must be contacted with details about the pumped liquid etc before the pump is returned for service Otherwise GRUNDFOS can refuse to accept the pump for service Possible costs of returning the pump are paid by the customer If a pump has been used for a liquid which is injurious to health or toxic the pump will be c...

Страница 12: ... rotation c The valves in the discharge pipe are partly closed blocked Check and clean replace the valves if necessary d The discharge pipe is partly choked by impurities ochre Clean replace the discharge pipe e The non return valve of the pump is partly blocked Pull out the pump and check replace the valve f The pump and the riser pipe are partly choked by impurities ochre Pull out the pump Check...

Страница 13: ... the full load current there are the following possible faults The contacts of the motor starter burnt Replace the con tacts Poor connection in leads possibly in the cable joint See item 3 Too high or too low supply voltage See item 1 The motor windings are short circuited or partly disjointed See item 3 Damaged pump is causing the motor to be overloaded Pull out the pump for overhaul The resistan...

Страница 14: ... Bride Flangia Brida Flange Φλάντζα Flens Fläns Laippa Flange Motor Motor Moteur Motore Motor Motor Κινητήρας Motor Motor Moottori Motor Direct On Line Starting Direktanlauf Démarrage direct Avviamento diretto Arranque directo Arranque directo Απευθείας Εκκίνηση Directe aanloop Direktstart Suorakäynnistys Direkte start Star Delta Starting Stern Dreieck Anlauf Démarrage étoile triangle Avviamento Y...

Страница 15: ... 3 x 400 V I 40 A L 140 m U 2 Lx L U 140 2 70 m q 25 mm 2 TM00 1346 5092 I 40 A U 2 U 3 x 400 V L 140 m Example U 3 x 380 V I 10 A L 120 m U 2 Lx L U 120 2 60 m q 6 mm 2 TM00 1345 5092 I 10 A U 2 U 3 x 380 V L 120 m ...

Страница 16: ...3 x 220 V I 5 A L 105 m U 3 Lx L U 105 3 35 m q 2 5 mm 2 TM00 1348 5092 I 5 A U 3 U 3 x 220 V L 105 m Example U 3 x 415 V I 100 A L 150 m U 3 Lx L U 150 3 50 m q 50 mm 2 TM00 1347 5092 I 100 A U 3 U 3 x 415 V L 150 m ...

Страница 17: ...112 ...

Страница 18: ...113 ...

Страница 19: ...114 ...

Страница 20: ...ps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia Deglava biznesa centrs Augusta Deglava ielā 60 LV 1035 Rīga Tālr 371 714 9640 7 149 641 Fakss 371 914 9646 Lithuania GRUNDFOS Pumps UAB Smolensko g 6 LT 03201 Vilnius Tel 370 52 395 430 Fax 370 52 395 431 Malaysia GRUNDFOS Pumps Sdn Bhd 7 ...