10.2 Guide for engine-driven generators in submersible pump applications
1- or 3-phase motor
[Hp]
Generator [kW]
Externally regulated
Internally regulated
0.33
1.5
1.2
0.5
2.0
1.5
0.75
3.0
2.0
1
4.0
2.5
1.5
5.0
3.0
2
7.5
4.0
3
10.0
5.0
5.0
15.0
7.5
7.5
20.0
10.0
10.0
30.0
15.0
15.0
40.0
20.0
20.0
60.0
25.0
25.0
75.0
30.0
30.0
100.0
40.0
40.0
100.0
50.0
50.0
150.0
60.0
60.0
175.0
75.0
75.0
250.0
100.0
100.0
300.0
150.0
125.0
375.0
175.0
150.0
450.0
200.0
200.0
600.0
275.0
Note:
•
The table is based on t176 °F (+80 °C) rise continuous
duty generators with 35 % maximum voltage dip during the
startup of single- and three-phase motors.
•
Contact the manufacturer of the generator to make sure the unit
has adequate capacity to run the submersible motor.
•
If the generator rating is in KVA instead of kilowatts, multiply the
above ratings by 1.25.