E
ngli
sh (
G
B)
32
Timer, cycle (relay 2)
For the
’Relay 2 > Timer cycle’
function, set the
following parameters:
•
Dosing time (t
1
)
•
Start delay (t
2
)
•
Cycle time (t
3
)
Fig. 37
Diagram
Timer, week (relay 2)
This function saves up to 16 relay on-times for a
week. The following settings can be made for each
relay switching operation in the
’Relay 2 >
Timer Week’
menu:
•
Procedure (No.)
•
On-time (duration)
•
Start time
•
Weekdays.
6.16.2 External stop
The pump can be stopped via an external
pulse, e. g. from a control room. When activating the
external stop pulse, the pump switches from the
operational state ’Running’ into the operational state
’Standby’. The corresponding symbol appears in the
Signal/error display (see section
The contact type is factory-set to closed contact
(=>NO). In the
’Setup > Inputs/outputs > External
stop’
menu, the setting can be changed to open
contact (=>NC).
6.16.3 Empty and low-level signals
In order to monitor the filling level in the
tank, a dual-level sensor can be connected to the
pump. The pump responds to the signals as follows:
Both signal inputs are allocated to the closed contact
(=>NO) in the factory. They can be re-allocated in
the
’Setup > Inputs/outputs’
menu to open contact
(=>NC).
6.17 Basic settings
All settings can be reset to the settings default upon
delivery in the
’Setup > Basic settings’
menu.
Selecting
’Save customer settings’
saves the current
configuration to the memory. This can then be
activated using
’Load customer settings’
.
The memory always contains the previously saved
configuration. Older memory data is overwritten.
T
M
04 1
124
21
1
0
Caution
Frequent disengagement from the
mains voltage, e. g. via a relay, can
result in damage to the pump
electronics and to the breakdown of the
pump. The dosing accuracy is also
reduced as a result of internal start
procedures.
Do not control the pump via the mains
voltage for dosing purposes!
Only use the ’External stop’ function to
start and stop the pump!
t
2
t
3
t
1
t
1
Sensor signal
Pump status
Low level
• Display is yellow
•
flashes
• Pump continues
running
Empty
• Display is red
•
flashes
• Pump stops
Содержание SMART Digital DDA
Страница 1: ...GRUNDFOS INSTRUCTIONS SMART Digital DDA Installation and operating instructions...
Страница 40: ...40...
Страница 41: ...41...