30
5.8 Chiller
* The values apply to the operating point, the maximum values are higher.
5.9 Heater
5.10 Brine tank
Supply voltage:
400 V, 50/60 Hz (3 PE)
Max. water temperature inlet:
30 °C
Water temperature outlet:
15 °C
Flow
[l/h]
Capacity
level Cl
2
(equivalent)
[g/h]
Ambient temperature range: 10-40 °C (type OLB), 5-45 °C (type cBoxX, Arctic)
Type
Cooling
capacity
[kW]
Power
consumption
[kW]*
Current
consumption
[A]*
Length
[mm]
Width
[mm]
Height
[mm]
Weight
[kg]
600
5000
OLB 12
10.0
5.6
11.4
800
1122
1511
230
900
7500
OLB 25
18.4
9.9
17.3
810
1270
1764
315
1200
10000
cBoxX 30
23.0
9.2
17.6
1240
830
2030
540
1800
15000
cBoxX 50
38.0
15.0
27.4
1240
830
2030
550
2400
20000
cBoxX 60
44.0
19.1
35.8
1240
830
2030
620
3600
30000
cBoxX 90
63.1
27.2
44.7
1840
830
2030
700
5100
45000
cBoxX 160
112.5
46.3
82.9
2665
1200
2030
1100
10200
2 x 45000
2 x cBoxX 160
2 x 112.5
2 x 46.3
2 x 82.9
2 x 2665
2 x 1200
2 x 2030
2 x 1100
20400
4 x 45000
Arctic 350
345.0
162.6
280.3
6500
2220
2200
4500
40800
8 x 45000
2 x Arctic 350
2 x 345.0
2 x 162.6
2 x 280.3
2 x 6500
2 x 2220
2 x 2200
2 x 4500
Flow
[l/h]
Capacity
level Cl
2
(equivalent)
[g/h]
Ambient temperature range: 10-50 °C (type OLB), 5-50 °C (type cBoxX, Arctic)
Type
Cooling
capacity
[kW]
Power
consumption
[kW]*
Current
consumption
[A]*
Length
[mm]
Width
[mm]
Height
[mm]
Weight
[kg]
600
5000
OLB 19
11.4
7.6
13.3
810
1270
1764
315
900
7500
cBoxX 30
23.0
9.2
17.6
1240
830
2030
540
1200
10000
cBoxX 40
25.7
12.0
21.9
1240
830
2030
540
1800
15000
cBoxX 50
38.0
17.5
31.5
1240
830
2030
550
2400
20000
cBoxX 70
43.0
20.8
35.9
1840
830
2030
650
3600
30000
cBoxX 100
63.4
31.0
53.3
1840
830
2030
720
5100
45000
cBoxX 180
110.0
52.3
89.9
3965
1200
2030
1300
10200
2 x 45000
2 x cBoxX 160
2 x 95.3
2 x 46.3
2 x 82.9
2 x 2665
2 x 1200
2 x 2030
2 x 1100
20400
4 x 45000
Arctic 380
345.0
230.4
375.9
7500
2220
2200
5000
40800
8 x 45000
2 x Arctic 380
2 x 345.0
2 x 230.4
2 x 375.9
2 x 7500
2 x 2220
2 x 2200
2 x 5000
Supply voltage:
400 V, 50/60 Hz (3 PE)
Min. water temperature inlet:
3 °C
Water temperature outlet:
15 °C
Flow
[l/h]
Capacity
level Cl
2
(equivalent)
[g/h]
Heating
capacity
[kW]
Type
Power
consumption
[kVA]
Flange
Fuse rating
[A]
Weight
[kg]
Heater
Control
panel
600
5000
8
HF/SE-10
10.5
DN 25
20
45
40
900
7500
13
HF/SE-15
16
DN 25
35
46
50
1200
10000
17
HF/SE-20
21
DN 25
50
47
70
1800
15000
25
HF/SE-30
31.5
DN 50
63
63
70
2400
20000
34
HF/SE-40
42
DN 50
80
73
70
3600
30000
50
HF/SE-60
63
DN 50
2 x 63
78
80
5100
45000
71
HF/SE-95
100
DN 80
2 x 100
135
100
10200
2 x 45000
142
HF/SE-175
184
DN 80
4 x 100
195
150
20400
4 x 45000
285
HF/SE-345
363
DN 100
6 x 125
320
250
40800
8 x 45000
570
HF/SE-560
588
DN 100
8 x 125
495
400
Soft water quality for operation
Drinking water quality, softened to: 1 °dH / 17.8 ppm CaCO
3
and less
Salt capacity
[kg]
Diameter
[m]
Height
[m]
Inlet
Outlet
Gravel bed weight
[kg]
3500
2.25
1.21
DN 25
DN 32
681
5000
2.48
1.05
DN 25
DN 32
1242
7000
2.48
1.35
DN 25
DN 32
1242