English (GB)
5
5. Approvals
5.1 Approval standards
All versions have been approved by LGA (Notified body under the
Construction Products Directive) according to EN 12050-1.
5.2 Explanation to the Ex approval
The explosion-proof version has been approved by DEKRA
according to the ATEX directive. The explosion protection
classification of the SEG AUTO
ADAPT
pump is Europe CE 0344
II 2 G Ex b c d ib IIB T4 Gb.
5.3 IEC countries (Australia and other countries)
For IEC countries, such as Australia and others, the explosion-
proof versions of SEG AUTO
ADAPT
pumps have been approved
by DEKRA, certificate no IECEx DEK 11.0026X, according to IEC
60079-0:2007, IEC 60079-1:2007 and IEC 60079-11:2006.
The explosion-protection classification of the pumps is Ex d ib IIB
T4 Gb.
Directive/
standard
Code
Description
ATEX
CE 0344
=
CE mark of conformity according to the ATEX directive 2014/34/EU.
0344 is the number of the notified body which has certified the quality system for ATEX.
= Explosion protection mark.
II
=
Equipment group according to the ATEX directive, defining the requirements applicable to the
equipment in this group.
2
=
Equipment category according to the ATEX directive, defining the requirements applicable to the
equipment in this category.
G
= Explosive atmospheres caused by gases, vapours or mists.
Harmonised
European
standard
Ex
= The equipment conforms to the harmonised European standard.
b
= Control of ignition sources according to EN 13463-6.
c
= Constructional safety according to EN 13463-5 and EN 13463-1.
d
= Flame-proof enclosure according to EN 60079-1:2007.
ib
= Intrinsic safety enclosure according to EN 60079-11:2007.
IIB
=
Classification of gases according to EN 60079-0:2009.
Gas group B includes gas group A.
T4
= Maximum surface temperature is 135 °C according to EN 60079-0.
Gb
= Equipment protection level (IEC).
Directive/
standard
Code
Description
IEC 60079-0,
IEC 60079-1 and
IEC 60079-11
Ex
= The equipment conforms to the harmonised European standard.
d
= Flame-proof enclosure according to IEC 60079-1:2007.
ib
= Intrinsic safety according to EN 60079-11:2007.
IIB
=
Classification of gases according to IEC 60079-0:2009.
Gas group B includes gas group A.
T4
= Maximum surface temperature is 135 °C according to IEC 60079-0:2006.
Gb
= Equipment protection level.
Содержание seg autoadapt
Страница 1: ...SEG AUTOAdapt 0 9 4 0 kW DIN 50 Hz Service instructions GRUNDFOS INSTRUCTIONS ...
Страница 19: ...English GB 19 13 Drawings 13 1 Sectional drawing 0 9 to 1 5 kW TM06 6109 0716 6a Single phase pump only ...
Страница 20: ...English GB 20 13 2 Exploded view 0 9 to 1 5 kW TM06 5750 0316 ...
Страница 21: ...English GB 21 13 3 Sectional drawing 2 6 to 4 0 kW TM06 6111 0716 6a ...
Страница 22: ...English GB 22 13 4 Exploded view 2 6 to 4 0 kW Fig 21 SEG AUTOADAPT 2 6 4 kW TM06 5770 0316 ...