Eng
lish (US)
8
Fig. 9
Plug type C and Dwith unscreened cable
Fig. 10
7-pole cable end for plug type C and D
Plug type C and D with 10-pole cable
Fig. 11
Plug type C and D with 10-pole unscreened cable
Fig. 12
10-pole unscreened cable end for plug type C and D
7. Electrical connection
Connect the free end of the cable to the mains or to the control
panel according to the Installation and operating instructions of
the selected product.
All the Installation and operating instructions of Grundfos
products are available on www.product-selection.grundfos.com
8. Service
8.1 Maintanance and repair
The assembled cable is maintenance-free and must not be
repaired. Cable condition must be checked regularly. Damaged
cable must be replaced.
If the cable is disconnected, the re-connection of the cable must
follow the instructions in section
8.2 Spare parts
The O-ring and the union nut are the only parts that can be
replaced.
9. Technical data
Operating temperature range: 32 to 104°F
Enclosure class: IP68
Maximum installation depth: 66 ft.
Voltage range: 200-575 VAC
Power range: 1.6
-
17 hp (1.2 -12.7 kW)
TM
07
6
591
21
2
0
T
M
07
6
5
9
2
22
20
TM
07
6
5
6
8
19
20
Yellow/Green
Yellow/Green
Y-connection
D-connection
Short circuit wires
Short circuit wires
1
2
3
1
2
3
4
5
6
4
5
6
TM
07
6
5
7
1
19
20
After cable installation, an earthing-continuity check
must be done.
Ensure proper earthing connection between the
screen of the cable and the control cabinet.
Ex assembled cable installation must be carried out
by Grundfos or a Grundfos-authorised service
workshop.
Ex assembled cable installation must be carried out
by Grundfos or a Grundfos-authorised service
workshop.
1
2
3
4
5
6
7
8
9
Yellow/Green
FM
FM
FM
FM