PARAMETER LIST FOR REDI-FLO VFD
OPERATOR ADJUSTMENTS
OPERATOR ADJUSTABLE CONTROL FEATURES
Use flowchart below to change operator adjustable control features.
Page 13
Page 14
To Adjust Operator Adjustable Control Features, follow the following
instructions: (See Figure 8)
1. Disconnect Redi-Flo VFD from the power supply.
2. Remove front cover of VFD by losen the two phillips head screws.
3. Lift and set aside the cover to expose the mode keys in the center of the drive.
Use caution to avoid damage to the ribbon cable attaching the front cover to the
interior of the drive.
4. Setting aside the front cover place in a position so the LED display is visible.
5. Connect drive to the power supply.
6. Use the following flow chart to adjust operator adjustable control features.
Figure 8
CAUTION
The internals of the Redi-Flo VFD contain
High Voltages! Extreme caution should be
exercised when making adjustments.
Phillips screws
Note: Shaded functions can be changed during operation.
NO.
DESCRIPTION
RANGE
UNITS
DEFAULT
F00
RF2 Max. Output Frequency
100.0-400.0 Hz
1.0 Hz
400.0 Hz
F01
RF2 Min. Output Frequency
0.0-100.0 Hz
1.0 Hz
25.0 Hz
F02
RF4 Max. Output Frequency
30.0-100.0 Hz
1.0 Hz
100.0 Hz
F03
RF4 Min. Output Frequency
0.0-30.0 Hz
1.0 Hz
25.0 Hz
F04
Acceleration Time (to 100/400 Hz)
0.5-10.0 Sec.
0.5 Sec.
5.0 Sec.
F05
Deceleration Time (from 100/400 Hz)
0.5-10.0 Sec.
0.5 Sec.
5.0 Sec.
F06
Torque Boost (in % max.)
0-30%
1%
0%
F07
Base Frequency Select
50 or 60 Hz
Hz
60 Hz
F08
Motor Overload Level Im depends uponRF2/RF4
50-110% Im
% Im
110%
F09
Input Undercurrent Detection Disable
0
0= Disabled
0-1
(Disabled)
1= Enabled
F10
Input Undercurrent Detection Level
10-60% (1.6-9.6A)
% Im
30%
F11
Input Undercurrent Restart Time
1-99 mins.
1 min.
1 min.
F12
Switching Frequency
0-2
-
1 (7.8kHz)
0= 15.6 kHz
1= 7.8 kHz
2= 3.9 kHz
F13
Input Current Enabled
0-1
-
0
0= Disabled (23A)
(Disabled)
1= Enabled (16A)
23A
F14
Auto Reference Signal
0-1
-
0
0= Disabled
(Disabled)
1= Enabled
F15
No Motor Load
0-1
-
1
0= Disabled
(Enabled)
1= Enabled