15.5.1 Display language (4.5.1)
Fig. 27
Display language
Select the display language of the CU 361.
Possible settings:
•
English
•
German
•
French
•
Dutch
•
Danish.
Factory setting
The display language is English. It can be changed at start-up.
15.5.2 Units (4.5.2)
Select measuring units for the various parameters shown in the
display.
Fig. 28
Units
For the basic setting, choose between SI and US units. It is also
possible to select other units for the individual parameters.
Setting range
Factory setting
The CU 361 has been factory-set to SI units.
15.5.3 Date and time (4.5.3)
Set the date and time and select how they are to be shown in the
display.
Fig. 29
Date and time
The clock has a built-in rechargeable power supply which can
supply the clock for up to 20 days if the power supply to the
CU 361 is interrupted.
If the clock has been without power for more than 20 days, it must
be set again.
Setting range
The date can be set as day, month and year. The time can be set
as a 24-hour clock showing hours and minutes.
There are three formats:
Factory setting
Local time.
Di
s
p
la
y
_
4
.5.
1
Di
s
p
la
y
_
4
.5.
2
Parameter
Basic setting
Possible units
SI
US
Pressure
bar
psi
kPa, MPa, mbar, bar, m,
psi
Flow rate
m
3
/h
gpm
m
3
/s, m
3
/h, l/s, gpm,
yd
3
/s, yd
3
/min, yd
3
/h
Volume
m
3
gal
l, m
3
, gal, yd
3
Level
m
ft
m, cm, ft, in
Note
If units are changed from SI to US and vice versa,
all individually set parameters are changed to the
basic setting in question.
D
is
pl
ay_
4
.5
.3
Examples of format
2010-04-21 11:49
21-04-2010 11:49
4/21/2010 11:49 am
Note
If the CU 361 has been without power for more
than 20 days since it left the factory, the clock
may have returned to the original setting:
01-01-2008 0:00.
Date and time may have been changed during the
setting of the CU 361.
There is no automatic changeover to and from
daylight-saving time.