English (GB)
15
15.2 Booster pump settings (4.2)
Fig. 18
Booster pump settings
In this menu, the booster pump setpoint is set and the maximum
allowed discharge pressure (p
max
) can be set with 1 bar
increments. The chosen setting prevents the setpoint from being
set to a value higher than p
max
.
Factory setting
15.3 Inputs and outputs (4.3)
Fig. 19
Inputs and outputs
In this menu, the various analog and digital signal transmitters
are configured.
This menu has these submenus:
•
Digital inputs
•
Analog inputs
•
Digital outputs.
15.3.1 Digital inputs (4.3.1)
As standard, the CU 361 has three digital inputs. Furthermore the
RCME incorporates an IO 351B module with nine digital inputs.
In this menu, the digital inputs of the CU 361 and IO 351B can be
set. The inputs DI1, DI2 and DI3 of the CU 361 have been
factory-configured as have DI1 of the IO 351B module.
The remaining eight inputs can be defined by the user.
In the display, all digital inputs are shown so that their physical
position in the control cabinet can be identified.
Example
DI1 (IO 351B-41) [10]:
For further information on the connection of the various digital
inputs, see the wiring diagram supplied with the control cabinet.
This display shows the three digital inputs of the CU 361 and the
nine digital inputs of the IO 351B.
Fig. 20
Digital inputs
Standard configuration:
Disp
lay_
4
.2
Pressure
Setting
Setpoint
4.5 bar
p
max
5 bar
D
is
pl
a
y
_4.
3
DI1
Digital input 1
IO 351B-41
IO 351B, GENIbus number 41
[10]
Terminal 10
Di
spla
y_
4.3.1
DI1 (CU 361) [10]
Fault signal from feed pump
DI2 (CU 361) [12]
Fault signal from booster pump
DI3 (CU 361) [14]
Not used
DI1 (IO 351B-41) [10]
Not used
DI2 (IO 351B-41) [12]
Not used
DI3 (IO 351B-41) [14]
Not used
DI4 (IO 351B-41) [16]
Not used
DI5 (IO 351B-41) [20]
Not used
DI6 (IO 351B-41) [24]
Not used
DI7 (IO 351B-41) [42]
Not used
DI8 (IO 351B-41) [44]
Not used
DI9 (IO 351B-41) [46]
Not used