8.2 Technical data, three-phase motors
DANGER
Electric shock
Death or serious personal injury
‐
Use the recommended fuse size.
Supply voltage
•
3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
•
3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Check that the supply voltage and frequency correspond to the values stated on the nameplate.
Recommended size of fuse or circuit breaker
3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
Motor size [kW]
Minimum [A]
Maximum [A]
0.25 - 1.1
6
6
1.5
6
10
2.2
6
16
3
10
16
4
13
16
5.5
16
32
7.5
20
32
11
32
32
3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE
Motor size [kW]
Minimum [A]
Maximum [A]
1.1
10
20
1.5
10
20
2.2
13
35
3
16
35
4
25
35
5.5
32
35
You can use standard as well as quick-blow or slow-blow fuses.
Related information
4.2.6.1 Overvoltage and undervoltage protection
8.2.1 Leakage current (AC)
The leakage currents are measured without any load on the shaft and in accordance with EN 61800-5-1:2007.
•
3 x 380-500 V - 10 %/+ 10 %, 50/60 Hz, PE
•
3 x 200-240 V - 10 %/+ 10 %, 50/60 Hz, PE.
Speed [min
-1
]
Power [kW]
Mains voltage [V]
Leakage current [mA]
1400-2000/1450-2200
0.25 - 1.5
≤ 400
< 3.5
> 400
< 5
2.2 - 4
≤ 400
< 3.5
> 400
< 3.5
5.5 - 7.5
≤ 400
< 3.5
> 400
< 5
2900-4000
0.25 - 2.2
1.5 - 2.2
≤ 400
< 3.5
> 400
< 5
3 - 5.5
≤ 400
< 3.5
> 400
< 3.5
7.5 - 11
≤ 400
< 3.5
> 400
< 5