33. Overview of inputs and outputs
DI: Digital input
DO: Digital output
AI: Analog input
NC: Normally closed contact
NO: Normally open contact
C:
Common.
Position numbers, see fig.
16
.
Group Terminal Designation
Data
Diagram
1
L
Connection to phase
conductor
1 x 100-240 VAC ± 10 %, 50/60 Hz
N
Connection to neutral
conductor
PE
Connection to
protective earth
2
A1
RS-485 A
GENIbus
(Fix the screen with a cable clamp.)
Y1
RS-485 GND
B1
RS-485 B
Functional earth
3
Connection to external fieldbus, see installation and operating instructions for the CIM module.
4
0 V
Connection to battery
Backup battery
+12 VDC
5
10
DI1
Digital input
11
GND
12
DI2
13
GND
14
DI3
All terminals (except mains terminals) must only be connected to
voltages not exceeding 16 V
rms
and 22.6 V
peak
or 35 VDC.
6
Ethernet RJ45
External computing devices connected to the Ethernet connection must
comply with the standards IEC 60950 and UL 60950.
7
GENIbus
Service connection
8
47
+24 V
Supply to sensor.
Short-circuit-protected 30 mA
50
+24 V
Supply to sensor.
Short-circuit-protected 30 mA
51
AI1
Input for analog signal,
0-20/4-20 mA or 0-10 V
53
+24 V
Supply to sensor.
Short-circuit-protected 30 mA
54
AI2
Input for analog signal,
0-20/4-20 mA or 0-10 V
57
AI3
58
GND*
All terminals (except mains terminals) must only be connected to
voltages not exceeding 16 V
rms
and 22.6 V
peak
or 35 VDC.
L
N
CU 3X2
L
N
PE
A
Y
B
CU 3X2
IO 351
A1
Y1
B1
14
13
12
10
11
57
54
53
50
51
58
1
2
3
47
72
CU 35
2