6.3 Synchronous motors
Pumps fitted with synchronous motors must be
connected to a Grundfos CUE frequency converter.
1
4
TM044289
Example of installation without filter
Symbol
Designation
1
CUE
4
Standard motor
One line
Unscreened cable
Double line
Screened cable
Synchronous motors must not be
connected directly to mains supply.
The CUE must be of T/C CUE203 followed by
additional numbers and characters. See the CUE
Installation and operating instruction to setup
frequency driver together with synchronous motor.
If another frequency driver brand other than CUE is
required or specified, contact Grundfos.
T/C: CUE203 P1M2T5E20H1BXCXXXSXXXXAXBXCXXXXDX
Prod. no: 12345678
S/N: 123456G234
IN: 3x380-500 V 50/60Hz 3.7A
OUT: 3x0-Vin 0-100Hz 4.1 A 2.8 kVA
CHASSIS/IP20 Tamb. 45C/122F
IIIIIIIIIIIBAR CODEIIIIIIIIIII
MADE IN DENMARK
Listed 76X1 E134261 Ind. Contr. Eq.
See manual for prefuse
CAUTION:
SEE MANUAL / VOIR MANUEL
WARNING:
STORED CHARGE DO NOT TOUCH UNTIL
4 MIN AFTER DISCONNECTION
CHARGE RESIDUELLE, ATTENDRE
4 MIN APRES DECONNEXION
1.5 kW (400V)
TM077181
Example of CUE nameplate
Text description
T/C
CUE (product name)
203... (internal code)
6.4 Frequency converter operation
All three-phase motors can be connected to a
frequency converter.
Frequency converter operation will often expose the
motor insulation system to a heavier load and cause
the motor to be more noisy than usual due to eddy
currents caused by voltage peaks.
A large motor driven via a frequency converter will be
loaded by bearing currents.
Check these operating conditions if the pump is
driven via a frequency converter:
Operating
conditions
Action
2-pole motors from
45 kW, 4-pole
motors from
37 kW and 6-pole
motors from 30 kW
Check that one of the motor
bearings is electrically
isolated.
Contact Grundfos.
Noise critical
applications
Fit an output filter between the
motor and the frequency
converter. This reduces the
voltage peaks and thus the
noise.
Particularly noise
critical applications
Fit a sinusoidal filter.
Cable length
Fit a cable that meets the
specifications laid down by the
frequency converter supplier.
The length of the cable
between motor and frequency
converter affects the motor
load.
Supply voltage up
to 500 V
Check that the motor is
suitable for frequency
converter operation.
Supply voltage
between 500 V and
690 V
Fit a sinusoidal filter between
the motor and the frequency
converter which reduces the
voltage peaks and thus the
noise, or check that the motor
has reinforced insulation.
Supply voltage of
690 V and higher
Fit a sinusoidal filter and check
that the motor has reinforced
insulation.
30
English (GB)