3. Mounting and setting of dosing 

monitor

1. Mount the monitor (the example below shows a 

monitor mounted on the suction side of the 
pump). The monitor must always be mounted 
vertically.

2. Connect the monitor to the pump level input.

3. Set the level input to "MONITOR".

Fig. 3 

4. Open the bypass valve.

5. Set the pump to operation at maximum capacity.

6. Prime the pump and the bypass channel.

7. Close the bypass valve and prime the floater 

channel.

8. Open the bypass valve and check that the pump 

is in alarm mode (the red indicator light is on).

9. Close the bypass valve gradually and adjust the 

contact screw until the floater jumps sufficiently 
and the pump changes over to normal operation 
(the red indicator light is off).

Fig. 4 

The function can be checked by letting air into the 
suction tube. This makes the pump change over to 
alarm mode (requires a certain counter pressure).

OK

T

M

02

 20

39

 33

01

Bypass 
channel

Bypass 
valve

Floater
Floater channel

Contact 
screw

Subject to alterations.

Содержание Dosing monitor

Страница 1: ...Dosing monitor GRUNDFOS INSTRUCTIONS Installation and operating instructions...

Страница 2: ...2...

Страница 3: ...i n y funcionamiento 16 19 Installatie en bedieningsinstructies 22 Monterings och driftsinstruktion 25 Asennus ja k ytt ohjeet 28 Monterings og driftsinstruktion 31 Instrukcja monta u i eksploatacji 3...

Страница 4: ...as in the dosing head When used together with a DME pump the monitor will only operate if it is mounted on the suction side of the pump When used together with a DMS pump the monitor will operate if i...

Страница 5: ...t will be on and the alarm output if any will be activated variant AR For each correct stroke the counter is reset and the alarm output if any is deactivated 2 3 Operation with vent valve Fig 2 It is...

Страница 6: ...ose the bypass valve and prime the floater channel 8 Open the bypass valve and check that the pump is in alarm mode the red indicator light is on 9 Close the bypass valve gradually and adjust the cont...

Страница 7: ...61...

Страница 8: ...62...

Страница 9: ...efax 81 53 484 1014 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135 916 Seoul Korea Phone 82 2 5317 600 Telefax 82 2 5633 725 Latvia SIA GRUNDFOS Pumps Latvia D...

Страница 10: ...www grundfos com Being responsible is our foundation Thinking ahead makes it possible Innovation is the essence 96470727 1105 216 Repl 96470727 0303 96488980 0303...

Отзывы: