8.2 Intended use

The DID is designed for online monitoring of water quality 
parameters and offers control functions for these parameters.
The DID must be used in accordance with the instructions given 
in this manual. The values mentioned in this manual must be 
observed.

8.3 Functional principle

The CU 382 control unit has a display and 7 operating buttons on 
the front. The operating software starts automatically when the 
CU 382 is powered-on.
The CU 382 control unit collects and displays readings from all 
sensors via a digital bus connection. The CU 382 control unit 
includes a PID (Proportional-Integral-Derivative) controller. With 
the PID controller and dosing units, a closed control loop can be 
set up.
The hydraulic part of the DID manages the complete water flow 
from the inlet to the outlet. This includes filtration, pressure 
reduction, flow restriction and flow control. The DID comprises 
specifically designed flow cells for mounting of the sensors and 
appropriate sampling.

8.4 Identification

8.4.1 Nameplate

Fig. 6

Nameplate on the CU 382 control unit

Fig. 7

Nameplate on the DID

8.4.2 Type key

Example: DID-3 BF3-FCL2/TCL2/pH

T

M

06

 59

20

 03

16

Pos. Description

1

Manufacturer and country of origin

2

s::can product name

3

Number of sensors

4

Bar code

5

Serial number (S/N)

6

Enclosure class

7

Certification marks

8

QR code

9

Type

10

Voltage [V]

11

Frequency [Hz]

12

Power consumption [W]

13

Humidity limits

14

Temperature limits

1

2
3

5

7

8

10,11,12

13

14

4

6

9

TM

06

 8

6

10

 08

17

Pos. Description

1

s::can product name

2

Parameter

3

Mounting type

4

Type

5

Part number

6

Bar code

7

Serial number (S/N)

Code

Description

CU 382 
control unit 
variants

DID-1

CU 382-1 for 1 par 
temperature, 100-240 VAC, 50-60 Hz

DID-3

CU 382-3 for 3 para 
temperature, 100-240 VAC, 50-60 Hz

Installation 
variant

BF1

Bypass flow cell, 1 sensor

BF3

Bypass flow cell, 3 sensors

TI1

Tank immersion, 1 sensor

TI2

Tank immersion, 2 sensors

Parameters/
Sensors

FCL2

Free chlorine 0-2 ppm

FCL20

Free chlorine 0-20 ppm

TCL2

Total chlorine 0-2 ppm

TCL20

Total chlorine 0-20 ppm

CDI2

Chlorine dioxide 0-2 ppm

CDI20

Chlorine dioxide 0-20 ppm

HP2

Hydrogen peroxide 0-200 ppm

HP20

Hydrogen peroxide 0-2000 ppm

PA2

Peracetic acid 0-200 ppm

PA20

Peracetic acid 0-2000 ppm

pH

pH 2-12 pH up to 10 bar and 70 °C

ORP

ORP, -2000 mV to +2000 mV up to 10 
bar, up to 70 °C

CND

Conductivity, 1-500,000 µS/cm (2-42 
PSU), up to 20 bar, up to 70 °C 

Remarks:
• All sensors include temperature measurement
• Disinfectant parameters (FCL,TCL, CDI, HP or PA) are only 

possible with BF1 or BF3

• BF1 and BF3 include flow detection
• BF1 and BF3 systems include 1.0 m sensor cables
• Installation variants TI1 and TI2 are only possible for 

parameters PH, ORP or CND

• TI1 and TI2 systems include 7.5 m sensor cable(s)
• Mains cable is generally not included, please select and order 

from accessories list.

1

2

3
4

5

6

7

Содержание DID BF1

Страница 1: ...DID Installation and operating instructions GRUNDFOS INSTRUCTIONS Other languages http net grundfos com qr i 99037650...

Страница 2: ...ety instructions 3 3 Receiving the product 3 3 1 Inspecting the product 3 3 2 Transporting the product 3 4 Installation 3 4 1 Installation location 3 4 2 Installation of the DID 3 4 3 Hydraulic connec...

Страница 3: ...installation of the DID with flow cell on a flat wall See also sections 8 Product introduction and 12 4 Dimensions DID with sensor for tank immersion The CU 382 control unit of the DID with sensor for...

Страница 4: ...ease of the flow 5 Starting up the product 5 1 Initial startup 1 Connect all sensors to the CU 382 control unit See also section 6 2 Connecting the sensors to the CU 382 control unit 2 Slowly open the...

Страница 5: ...ialisation process Connect only the sensor you want to initialise to the CU 382 An individual address is allocated to the initialised sensor If no sensor was connected before the CU 382 jumps into the...

Страница 6: ...f DID with flow cell Fig 5 Components of DID with immersed sensor TM06 8088 3416 9 5 4 3 2 1 11 10 10 12 13 14 15 15 15 15 7 6 6a 8 18 T OK W X S 19 6c 6b TM06 8089 3416 Pos Description 1 Water inlet...

Страница 7: ...n marks 8 QR code 9 Type 10 Voltage V 11 Frequency Hz 12 Power consumption W 13 Humidity limits 14 Temperature limits 1 2 3 5 7 8 10 11 12 13 14 4 6 9 TM06 8610 0817 Pos Description 1 s can product na...

Страница 8: ...Moves the marker to the line above The first character of the selected line is a triangle Increases values Function button Enters the setup menus Disables or deletes values Left button Moves the mark...

Страница 9: ...05B1 pH 15 YYYY MM DD Serial 9999999 9 49 Type PID Running ls below Waiting 1 s Temp pH 4 20mA 2 lower alarm limit YYYY MM DD hh nn ss 22 1 C AV SP 6 86 7 00 ext General setup Parameter setup Controll...

Страница 10: ...0mA digital outputs PULSE or PWM AV SP AV is the actual value input parameter reading SP is the setpoint desired value of the input parameter reading Source of the setpoint External Manual AP001 A1 1...

Страница 11: ...he Up and Down buttons Confirm with OK To add a MODBUS sensor select Add MODBUS sensor with the Up and Down buttons Confirm with OK The MODBUS port for a new sensor is searched and the new sensor is a...

Страница 12: ...e configured in the MODBUS slave menu Changing the Modbus address 1 Select Address with the Up and Down buttons Confirm with OK 2 Change the address value with the Up and Down buttons Confirm with OK...

Страница 13: ...Digital Input Read in all digital inputs Internal Sensors Read in all internal sensors USB Measure the performance of the USB stick Date Time Set the time and the date Hardware Read out the hardware r...

Страница 14: ...he second reference solution Select the value in the Lab 2 field with the Up and Down buttons Confirm with OK Use a temperature compensated value 11 Select Sample 2 with the Up and Down buttons Confir...

Страница 15: ...ith the Up and Down buttons Confirm with OK 2 The default display settings are loaded from the sensor All modifications of the display settings are documented in the logbook of the CU 382 control unit...

Страница 16: ...ut settings menu a parameter can be allocated to an analog output or a digital output Analog outputs Parameter values between these two limits are calculated according to a linear calibration Assignin...

Страница 17: ...ect Period s with the Up and Down buttons Confirm with OK 2 Change the value for the duration of one pulse with the Up Down Left and Right buttons Confirm with OK 9 4 7 Parameter info The Parameter in...

Страница 18: ...e type to Manual 1 Select Type with the Up and Down buttons Confirm with OK 2 Select Manual with the Up and Down buttons Confirm with OK Changing the setpoint of the controller 1 Select Setpoint with...

Страница 19: ...1 Select D factor with the Up and Down buttons Confirm with OK 2 Change the disturbance factor with the Up Down Left and Right buttons Confirm with OK Changing the direction of the controller 1 Select...

Страница 20: ...er that can be changed is the maximum of pulses min for 100 output Changing the maximum of pulses min for 100 output 1 Select Pulses Min with the Up and Down buttons Confirm with OK 2 Change the maxim...

Страница 21: ...all logfiles to the USB stick 1 Select Copy logfile with the Up and Down buttons 2 Confirm with OK to copy the data to the USB stick Deleting all logfiles 1 Select Delete logs with the Up and Down but...

Страница 22: ...arefully with water and a soft brush 8 Screw in the flow detector back 9 Reconnect the wires of the flow detector to the CU 382 10 Refit the hose 11 Screw on the hose connection 10 1 3 Sensor See the...

Страница 23: ...layed DID All hoses and fittings are tight CU 382 control unit The digital output of the flow detector is ok Outlet Water is flowing out of the outlet hose Water is visible within the hoses Flow cell...

Страница 24: ...s no flow a The inlet valve is closed Open the inlet valve b The inlet strainer is blocked Clean the inlet strainer 8 Water is not visible in the hoses a The inlet valve is closed Open the inlet valve...

Страница 25: ...n data Internal thread of inlet and outlet Rp1 2 Size of inlet and outlet connection thread G 5 8 Inlet outlet hose connections metric ID OD mm 4 6 6 9 6 12 or 9 12 Inlet outlet hose connections inch...

Страница 26: ...age VAC 240 Maximal switchable load A 6 Maximal number of operating cycles VA 600 Required external protection Depending on the load additional snubber circuits may be required Description Unit D 320...

Страница 27: ...5 Terminal connections 4 x M12 cable gland entry one used by flow switch 1 x M16 cable gland entry IP rating IP65 Memory MB 512 industrial grade SLC Display mm 128 x 64 graphical display 70 x 40 viewi...

Страница 28: ...3 FCL2 ORP 4 710 8 765 DID 3 BF3 FCL2 PH ORP 4 960 9 165 DID 1 BF1 PH 4 250 8 085 DID 1 TI1 PH 2 075 5 875 DID 1 TI1 ORP 2 075 5 875 DID 3 TI2 ORP PH 2 850 6 800 DID 3 BF3 ORP PH 4 700 8 755 DID 1 BF1...

Страница 29: ...tact the nearest Grundfos company or service workshop TM06 5897 0216 TM06 6025 0416 Fig 12 Dimensions of CU 382 control unit front and side in mm Fig 13 Dimensions of CU 382 control unit for wall moun...

Страница 30: ...t of the sensors The sensors must always be immersed in water Avoid siphon effect Use a vented outlet or a pressure loading valve Avoid power loss of the sensors that are equipped with electrolyte and...

Страница 31: ...Documents as listed Type of product Measurement Process Control Name of product DID Model number D 320 GF1 230 D 320 GF3 230 Low Voltage Directive 2014 35 EU Standard used EN 61010 1 2010 RoHS2 2011...

Страница 32: ...an GRUNDFOS Pumps K K 1 2 3 Shin Miyakoda Kita ku Hamamatsu 431 2103 Japan Phone 81 53 428 4760 Telefax 81 53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam...

Страница 33: ...NDFOS Pumps K K 1 2 3 Shin Miyakoda Kita ku Hamamatsu 431 2103 Japan Phone 81 53 428 4760 Telefax 81 53 428 5005 Korea GRUNDFOS Pumps Korea Ltd 6th Floor Aju Building 679 5 Yeoksam dong Kangnam ku 135...

Страница 34: ...1168 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding...

Отзывы: