8.2 Intended use
The DID is designed for online monitoring of water quality
parameters and offers control functions for these parameters.
The DID must be used in accordance with the instructions given
in this manual. The values mentioned in this manual must be
observed.
8.3 Functional principle
The CU 382 control unit has a display and 7 operating buttons on
the front. The operating software starts automatically when the
CU 382 is powered-on.
The CU 382 control unit collects and displays readings from all
sensors via a digital bus connection. The CU 382 control unit
includes a PID (Proportional-Integral-Derivative) controller. With
the PID controller and dosing units, a closed control loop can be
set up.
The hydraulic part of the DID manages the complete water flow
from the inlet to the outlet. This includes filtration, pressure
reduction, flow restriction and flow control. The DID comprises
specifically designed flow cells for mounting of the sensors and
appropriate sampling.
8.4 Identification
8.4.1 Nameplate
Fig. 6
Nameplate on the CU 382 control unit
Fig. 7
Nameplate on the DID
8.4.2 Type key
Example: DID-3 BF3-FCL2/TCL2/pH
T
M
06
59
20
03
16
Pos. Description
1
Manufacturer and country of origin
2
s::can product name
3
Number of sensors
4
Bar code
5
Serial number (S/N)
6
Enclosure class
7
Certification marks
8
QR code
9
Type
10
Voltage [V]
11
Frequency [Hz]
12
Power consumption [W]
13
Humidity limits
14
Temperature limits
1
2
3
5
7
8
10,11,12
13
14
4
6
9
TM
06
8
6
10
08
17
Pos. Description
1
s::can product name
2
Parameter
3
Mounting type
4
Type
5
Part number
6
Bar code
7
Serial number (S/N)
Code
Description
CU 382
control unit
variants
DID-1
CU 382-1 for 1 par
temperature, 100-240 VAC, 50-60 Hz
DID-3
CU 382-3 for 3 para
temperature, 100-240 VAC, 50-60 Hz
Installation
variant
BF1
Bypass flow cell, 1 sensor
BF3
Bypass flow cell, 3 sensors
TI1
Tank immersion, 1 sensor
TI2
Tank immersion, 2 sensors
Parameters/
Sensors
FCL2
Free chlorine 0-2 ppm
FCL20
Free chlorine 0-20 ppm
TCL2
Total chlorine 0-2 ppm
TCL20
Total chlorine 0-20 ppm
CDI2
Chlorine dioxide 0-2 ppm
CDI20
Chlorine dioxide 0-20 ppm
HP2
Hydrogen peroxide 0-200 ppm
HP20
Hydrogen peroxide 0-2000 ppm
PA2
Peracetic acid 0-200 ppm
PA20
Peracetic acid 0-2000 ppm
pH
pH 2-12 pH up to 10 bar and 70 °C
ORP
ORP, -2000 mV to +2000 mV up to 10
bar, up to 70 °C
CND
Conductivity, 1-500,000 µS/cm (2-42
PSU), up to 20 bar, up to 70 °C
Remarks:
• All sensors include temperature measurement
• Disinfectant parameters (FCL,TCL, CDI, HP or PA) are only
possible with BF1 or BF3
• BF1 and BF3 include flow detection
• BF1 and BF3 systems include 1.0 m sensor cables
• Installation variants TI1 and TI2 are only possible for
parameters PH, ORP or CND
• TI1 and TI2 systems include 7.5 m sensor cable(s)
• Mains cable is generally not included, please select and order
from accessories list.