12.6.2 STO application
The STO signal must be SELV or PELV supplied.
European directive
Machinery Directive
(2006/42/EC)
EN ISO 13849-1
EN IEC 62061
EN IEC 61800-5-2
EMC Directive
(2004/108/EC)
EN 50011
EN 61000-6-3
EN 61800-3
Low Voltage Directive
(2006/95/EC)
EN 50178
EN 61800-5-1
Safety standards
Safety of machinery
EN ISO 13849-1,
IEC 62061, IEC
60204-1
Functional safety
IEC 61508-1 to -7,
IEC 61800-5-2
Safety function
IEC 61800-5-2 (Safe
Torque Off, STO)
IEC 60204-1 (Stop
Category 0)
Safety
performance
ISO 13849-1
Category
Cat 3
Diagnostic Coverage
DC: 90 %, medium
Mean Time to
Dangerous Failure
MTTFd: 14000
years, high
Performance Level
PL d
IEC 61508 / IEC 62061
Safety Integrity Level
SIL 2, SIL CL2
Probability of
Dangerous Failure per
Hour
PFH: 1E-10/h
High Demand Mode
Probability of
Dangerous Failure on
Demand
PFD: 1E-10
Low Demand Mode
Safe Failure Fraction
SFF: > 99 %
Hardware Fault
Tolerance
HFT: 0 (1oo1)
Proof Test Interval T1
20 years
Mission time TM
20 years
Reaction time
Input to output
response time
Maximum 20 ms
13. Disposing of the product
This product or parts of it must be disposed of in an environmentally
sound way.
1. Use the public or private waste collection service.
2. If this is not possible, contact the nearest Grundfos company or
service workshop.
3. Dispose of the waste battery through the national collective
schemes. If in doubt, contact your local Grundfos company.
The crossed-out wheelie bin symbol on a product
means that it must be disposed of separately from
household waste. When a product marked with this
symbol reaches its end of life, take it to a collection
point designated by the local waste disposal
authorities. The separate collection and recycling of
such products will help protect the environment and
human health.
See also end-of-life information at
45
English (GB)