5.9 Flange forces and torques
If not all loads reach the maximum permissible value stated in the tables below, one of these values may
exceed the normal limit. Contact Grundfos for further information.
Y-direction: Inlet or outlet
Z-direction: Direction of
chamber stack
X-direction: 90° from inlet or
outlet
TM040346
The following tables represent the values that apply according to the material quality.
Force limits for CR pumps
Flange
CR
Force, Y-direction
[lbf (N)]
Force, Z-direction
[lbf (N)]
Force, X-direction
[lbf (N)]
4" ANSI (DN 100)
95
282 (1256)
228 (1013)
253 (1125)
6" ANSI (DN 150)
125, 155
422 (1875)
342 (1519)
380 (1688)
8" ANSI (DN 200)
185, 215, 255
465 (2513)
455 (2025)
506 (2250)
Force limits for CRN pumps
Flange
CRN
Force, Y-direction
[lbf (N)]
Force, Z-direction
[lbf (N)]
Force, X-direction
[lbf (N)]
4" ANSI (DN 100)
95
565 (2513)
455 (2025)
506 (2250)
6" ANSI (DN 150)
125, 155
843 (3750)
683 (3038)
759 (3375)
8" ANSI (DN 200)
185, 215, 255
1130 (5025)
910 (4050)
1012 (4500)
Torque limits for CR pumps
Flange
CR
Torque, Y-direction
[lbf (N)]
Torque, Z-direction
[lbf (N)]
Torque, X-
direction
[lbf (N)]
4" ANSI (DN 100) 95
84 (375)
107 (475)
141 (625)
6" ANSI (DN 150) 125, 155
141 (625)
174 (775)
225 (1000)
8" ANSI (DN 200) 185, 215, 255
202 (900)
242 (1075)
309 (1375)
19