11.4 Configuration / basic settings
11.4.1 Changing to the "Configuration" menu
One of the following menus is displayed in the
display mode.
1. Press [OK] to change to the "Parameter" menu.
2. Press [OK] several times until the "Configuration"
menu is displayed.
3. Press the [Up] button to set "Configuration ON".
4. Press [OK] to change to the "Configuration"
menu.
11.4.2 Selecting operating language
This item appears first in the "Configuration" menu
and does not need to be selected.
1. Select the desired language by pressing the [Up]
or [Down] button.
Possible values:
•
English
•
French
•
German.
2. Confirm by pressing [OK].
11.4.3 Selecting the number of connected
sensors
1. Select the number of connected sensors by
pressing the [Up] and [Down] buttons.
Possible values:
•
1 sensor (default setting)
•
2 sensors.
2. Confirm by pressing [OK].
11.4.4 Selecting the operating mode of the
current outputs
1. Select the desired operating mode by pressing
the
[Up] and [Down]
buttons.
Possible values:
•
0-20 mA (default setting)
•
4-20 mA.
2. Confirm by pressing [OK].
Note
If a sprinkling installation is connected,
first shut off the water supply. On initial
start-up, the relevant limit value may be
exceeded during the sensor start-up
routine, which could trigger the sprinkling
installation.
The measuring parameter does not have
to be set in the software (or device). It is
selected using the corresponding sensor.
M1 or M2 stands for measured value 1
(coming from sensor 1) or measured value
2 (coming from sensor 2).
Measured
value
x.xx ppm
M1
x.xx ppm
M2
x.xx ppm
Configuration
OFF
*Configuration*
Language
English
No. of sensors
1 sensor
mA signal
0-20 mA