13. Fault finding

Warning

Before removing the terminal box cover, make sure that the power supply has been switched 
off.

The pumped liquid may be scalding hot and under high pressure. Before any removal or 
dismantling of the pump, the system must therefore be drained, or the isolating valves on 
either side of the pump must be closed.

Fault

Cause

Remedy

1.

The pump does not run.

a)

Supply failure.

Switch on the switch. Check cables 
and cable connections for defects 
and loose connections.

b)

Fuses are blown.

Check cables and cable connections 
for defects, and replace the fuses.

c)

Motor protection tripped.

See 2. a), b), c), d), e), f).

d)

Control-current circuit 
defective.

Repair or replace the control-current 
circuit.

2.

Motor-protective circuit 
breaker has tripped 
(trips out immediately when 
supply is switched on).

a)

Fuses are blown.

See 1. b).

b)

Contacts of the 
motor-protective circuit 
breaker or magnet coil 
defective.

Replace the contacts of the 
motor-protective circuit breaker, 
the magnet coil or the entire 
motor-protective circuit breaker.

c)

Cable connection is loose or 
faulty.

Check cables and cable connections 
for defects, and replace the fuses.

d)

Motor winding is defective.

Repair or replace the motor.

e)

The pump is mechanically 
blocked.

Switch off the power supply, and 
clean or repair the pump.

f)

The setting of the 
motor-protective circuit 
breaker is too low.

Set the motor-protective circuit 
breaker according to the rated 
current of the motor (I

1/1

). 

See nameplate.

3.

The motor-protective circuit 
breaker trips out 
occasionally.

a)

The setting of the 
motor-protective circuit 
breaker is too low.

See 2. f).

b)

Periodic supply failure.

See 2. c).

c)

Periodically low voltage.

Check cables and cable connections 
for defects and loose connections. 
Check that the supply cable of the 
pump is correctly sized.

4.

The motor-protective circuit 
breaker has not tripped out, 
but the pump is 
inadvertently out of 
operation.

a)

See 1. a), b), d) and 2. e).

5.

The pump performance is 
unstable.

a)

Pump inlet pressure too low.

Check the inlet conditions of the 
pump. 

b)

Suction pipe is partly blocked 
by impurities.

Remove and clean the suction pipe.

c)

Leakage in suction pipe.

Remove and repair the suction pipe.

d)

Air in suction pipe or pump.

Vent the suction pipe/pump. 
Check the inlet conditions of the 
pump.

Содержание CMV

Страница 1: ...CMV Installation and operating instructions GRUNDFOS INSTRUCTIONS ...

Страница 2: ... декларация за съответствие е валидна само когато е публикувана като част от инструкциите за монтаж и експлоатация на Grundfos номер на публикацията 97907165 0513 CZ ES prohlášení o shodě My firma Grundfos prohlašujeme na svou plnou odpovědnost že výrobek CMV na nějž se toto prohlášení vztahuje je v souladu s ustanoveními směrnice Rady pro sblížení právních předpisů členských států Evropského spol...

Страница 3: ...ς εντύπου 97907165 0513 ES Declaración CE de conformidad Nosotros Grundfos declaramos bajo nuestra entera responsabilidad que los productos CMV a los cuales se refiere esta declaración están conformes con las Directivas del Consejo en la aproximación de las leyes de las Estados Miembros del EM Directiva de Maquinaria 2006 42 CE Normas aplicadas EN 809 1998 A1 2009 y EN 60204 1 2006 Directiva de Ba...

Страница 4: ...ек ғана Грундфос компаниясының орнату жəне пайдалану нұсқасының бөлімі ретінде жарамды баспаға шыққан нөмірі 97907165 0513 HU EK megfelelőségi nyilatkozat Mi a Grundfos egyedüli felelősséggel kijelentjük hogy a CMV termékek amelyekre jelen nyilatkozik vonatkozik megfelelnek az Európai Unió tagállamainak jogi irányelveit összehangoló tanács alábbi előírásainak Gépek 2006 42 EK Alkalmazott szabványo...

Страница 5: ...e conformidade CE A Grundfos declara sob sua única responsabilidade que os produtos CMV aos quais diz respeito esta declaração estão em conformidade com as seguintes Directivas do Conselho sobre a aproximação das legislações dos Estados Membros da CE Directiva Máquinas 2006 42 CE Normas utilizadas EN 809 1998 A1 2009 e EN 60204 1 2006 Directiva Baixa Tensão 2006 95 CE Aplicável quando a potência n...

Страница 6: ...eye duyarlı tasarım Ecodesign Direktifi 2009 125 EC Elektrikli motorlar 640 2009 sayılı Komisyon Yönetmeliği Sadece IE2 veya IE3 işaretli trifaze Grundfos motorlar için geçerlidir Motor bilgi etiketine bakınız Kullanılan standart EN 60034 30 2009 Çevreye duyarlı tasarım Ecodesign Direktifi 2009 125 EC Devirdaim su pompaları 547 2012 sayılı Komisyon Yönetmeliği Yalnızca Minimum Enerji Verimlilik En...

Страница 7: ...12 1 Enclosure class 11 12 2 Sound pressure level 11 12 3 Frequency of starts and stops 11 12 4 Ambient temperature 11 12 5 Storage and transport temperature 11 12 6 Maximum system pressure and permissible liquid temperature 12 12 7 Minimum inlet pressure 12 12 8 Maximum inlet pressure 12 13 Fault finding 13 14 Further product documentation 14 14 1 Service documentation 14 15 Disposal 14 Warning P...

Страница 8: ...ump is installed above the liquid level a non return valve must be fitted in the suction pipe below the liquid level The pump must not be stressed by the pipework The pipework must be correctly sized taking due account of the pump inlet pressure If the pump is installed at the lowest point of the system impurities and sludge may accumulate in the pump Install the pipes so that air locks are avoide...

Страница 9: ...agram inside the terminal box cover Fig 3 Wiring diagram 7 4 Frequency converter operation All three phase motors can be connected to a frequency converter Depending on the frequency converter type this may cause increased acoustic noise from the motor Furthermore it may cause the motor to be exposed to detrimental voltage peaks MG 71 and MG 80 based motors with phase insulation are available on r...

Страница 10: ...oming supply wires Fig 5 Installation indicator The indicator can be placed in various positions on the motor but it must not be placed between the cooling fins close to the screws holding the fan cover The correct direction of rotation is also shown by arrows on the motor fan cover Caution Do not start the pump until it has been filled with liquid Warning The system may be under pressure and the ...

Страница 11: ... prevent corrosion and deposits in the pump 11 Service Before returning the pump to Grundfos for service the safety declaration at the end of these instructions must be filled in by authorised personnel and attached to the pump in a visible position If Grundfos is requested to service the pump it must be ensured that the pump is free from substances that can be injurious to health or toxic If the ...

Страница 12: ...etres head If the calculated value of H is positive the pump can operate with a maximum suction lift of H metres If the calculated value of H is negative a minimum suction head of H metres is required during operation to avoid cavitation Example pb 1 bar Pump type CMV 3 50 Hz Flow rate 4 m3 h NPSH from fig 8 page 16 3 3 metres head Hf 3 0 metres head Liquid temperature 90 C Hv from fig 10 page 17 ...

Страница 13: ...eaker c Cable connection is loose or faulty Check cables and cable connections for defects and replace the fuses d Motor winding is defective Repair or replace the motor e The pump is mechanically blocked Switch off the power supply and clean or repair the pump f The setting of the motor protective circuit breaker is too low Set the motor protective circuit breaker according to the rated current o...

Страница 14: ...pressure too low See 5 a b The suction pipe is partly clogged by impurities See 5 b c The foot or non return valve is stuck in its closed position Remove and clean repair or replace the valve d Leakage in suction pipe See 5 c e Air in suction pipe or pump See 5 d 7 The pump runs backwards when switched off a Leakage in suction pipe See 5 c b Foot or non return valve defective See 6 c c The foot va...

Страница 15: ...1 3 3 11 12 13 11 12 13 11 12 13 11 12 13 6 7 7 6 6 0 5 4 8 10 9 Q nom H nom H max 50 Hz m h 3 m m GPM PSI PSI Q nom H nom H max 60 Hz m h 3 m m GPM PSI PSI ȘP TM05 3823 1712 Made in Hungary DK 8850 BJERRINGBRO DENMARK IE2 Motor Type 50 Hz I 1 1 P2 kW V A HP 60 Hz I 1 1 P2 V A HP Capacitor uF V Capacitor uF V kW Eff IE2 Eff IE2 1 3 4 5 6 7 8 2 3 4 5 6 7 8 9 10 11 12 13 ...

Страница 16: ...urves for CMV 5 TM04 0459 0309 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 Q m h 0 1 2 3 4 5 6 7 8 m NPSH CM 3 60 Hz 50 Hz CMV 3 TM04 0460 0309 0 0 0 5 1 0 1 5 2 0 2 5 3 0 3 5 4 0 4 5 5 0 5 5 6 0 6 5 7 0 Q m h 0 1 2 3 4 5 6 7 8 9 m NPSH CM 5 60 Hz 50 Hz CMV 5 ...

Страница 17: ...Appendix 17 Fig 10 Vapour pressure TM00 3037 0800 20 15 12 10 8 0 6 0 5 0 4 0 3 0 2 0 1 0 0 8 0 6 0 4 0 3 0 2 0 1 1 5 120 110 90 100 80 70 60 50 40 30 20 10 0 Hv m tm C 150 130 140 25 35 45 40 30 ...

Страница 18: ...on has the pump been used ____________________ Fault description If possible please make a circle around the faulty part In case of an electrical fault please mark the terminal box Please give a short description of the fault We hereby declare that this product is free from hazardous chemicals biological and radioactive substances _________________________ _________________________ Date and signat...

Страница 19: ...19 ...

Страница 20: ...2 606 1691 Finland OY GRUNDFOS Pumput AB Mestarintie 11 FIN 01730 Vantaa Phone 358 0 207 889 900 Telefax 358 0 207 889 550 France Pompes GRUNDFOS Distribution S A Parc d Activités de Chesnes 57 rue de Malacombe F 38290 St Quentin Fallavier Lyon Tél 33 4 74 82 15 15 Télécopie 33 4 74 94 10 51 Germany GRUNDFOS GMBH Schlüterstr 33 40699 Erkrath Tel 49 0 211 929 69 0 Telefax 49 0 211 929 69 3799 e mai...

Страница 21: ...OS d o o Šlandrova 8b SI 1231 Ljubljana Črnuče Phone 386 1 568 0610 Telefax 386 1 568 0619 E mail slovenia grundfos si South Africa GRUNDFOS PTY LTD Corner Mountjoy and George Allen Roads Wilbart Ext 2 Bedfordview 2008 Phone 27 11 579 4800 Fax 27 11 455 6066 E mail lsmart grundfos com Spain Bombas GRUNDFOS España S A Camino de la Fuentecilla s n E 28110 Algete Madrid Tel 34 91 848 8800 Telefax 34 ...

Страница 22: ...07165 0513 ECM 1114950 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright Grundfos Holding A S ...

Отзывы: