7.7 Alarms and warnings
In the WarningCode module, the cause of a booster system
warning can be read. A warning has no influence on the booster
system operation.
In the FaultCode module, the cause of a booster system alarm
can be read. A booster system alarm always leads to a reaction in
the booster system operation, usually all pumps are stopped, but
some Hydro MPC or Control MPC alarms have programmable
alarm action types.
The complete list of possible alarm and warning codes is shown
below.
1)
For Hydro/Control MPC and Multi-E model H and later, it can
be automatic (A) or selectable Automatic/Manual (A/M).
2)
For Hydro/Control MPC and Multi-E model H and later, it can
be none or programmable (Prog.).
Event action programmable are Stop, Stop with delay, Min.,
UserDef, Max., Pumps in local, Emergency run.
The Hydro Multi-E model G is always stopped in case of an
alarm.
Module
Name
Description
3
WarningCode
Code for booster system warning.
4
FaultCode
Code for booster system alarm.
Code
Alarm/warning description
Reset type
1)
Action type
2)
3
External fault signal
A/M
Prog.
10
Communication fault, pump
A
None
80
Hardware fault, IO 351 pump module
A
None
80
Hardware fault, IO 351 I/O module
A
None
83
Verification error, EEPROM parameter area
A
None
88
Sensor fault, general measuring sensor
A
None
89
Signal fault, closed-loop feedback sensor
A/M
Prog.
91
Temperature sensor 1 signal fault
A/M
Prog.
157
Real Time Clock error
A
None
161
Sensor supply fault, 5 V
A
None
162
Sensor supply fault, 24 V
A
None
165
Signal fault, analog input A1
A/M
Prog.
166
Signal fault, analog input A2
A/M
Prog.
167
Signal fault, analog input A3
A/M
Prog.
175
Temperature sensor 2 signal fault
A/M
Prog.
190
Limit exceeded, supervised item 1
A/M
Prog.
191
Limit exceeded, supervised item 2
A/M
Prog.
203
Alarm on all pumps
A/M
Prog.
204
Inconsistency between sensors
A
None
208
Operation outside performance range
A/M
Prog.
210
High pressure
A/M
Prog.
211
Low pressure
A/M
Prog.
213
VFD not ready
A
None
214
Water shortage
A/M
Prog.
215
Soft pressure buildup timeout
A/M
Prog.
216
Pilot pump alarm
A
None
219
Pressure relief not adequate
A
None
231
Ethernet: No IP address from DHCP server
A
None
232
Ethernet: Auto-disabled due to misuse
A
None
248
Fault, battery/UPS
A
None
From device
Pump alarms. See section
7.9 Zone pump modules (ZonePumpModule,
-
None