52
11.2 Danfoss VLT 8000 factory settings
11.3 Danfoss VLT 8000 extended menu programming
Parameter
Function
Grundfos setting
Value
001
Language
English
0
002
Motor power
Motor nameplate
003
Motor voltage
Motor nameplate
004
Motor frequency
Motor nameplate
005
Motor current
Motor nameplate (SFA)
006
Motor speed
Motor nameplate (RPM)
201
Minimum frequency
20 Hz
202
Maximum frequency
62 Hz
207
Ramp up time
1.5 sec
208
Ramp down time
3 sec
323
Relay 1 function
Ready signal
1
326
Relay 2 function
Running
3
Parameter
Function
Grundfos setting
Value
007
Large readout
Frequency [Hz]
3
008
Small display readout
Motor voltage [V]
16
009
Small display readout
Motor current
5
010
Small display readout
Power [Hp]
6
101
Torque characteristics
VT low
2
113
Motor Preheater DC Current
0%
117
Motor Thermal Protection
ETR Trip 1
4
208
Automatic ramp-down
Disable
0
210
Reference type
External/preset
2
302
Pin 18
Start
1
303
Pin 19
Reverse and start
2
304
Pin 27
Safety interlock
3
308
Pin 53
Reference
1
309
Term. 53, min. scaling
0.0 V
310
Term. 53, max. scaling
10 V
325
Relay 01, off delay
1 sec.
400
Reset function
Automatic reset x 10
6
401
Automatic restart time
5 sec.
407
Switching frequency
4500
408
Interference reduction method
Fixed switching freq.
0
016
Lock for data change
Locked
1
www.motralec.com / [email protected] / 01.39.97.65.10
Содержание BoosterpaQ Hydro MPC
Страница 12: ...12 INSTALLATION AND STARTUP NOTES www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 54: ...54 Variable frequency drive setting notes www motralec com service commercial motralec com 01 39 97 65 10 ...
Страница 58: ...58 www motralec com service commercial motralec com 01 39 97 65 10 ...