7.10.3 Configuring the thermal power limit
1.
Enable the thermal power limit by setting BV,1 to 1.
2.
Configure the limit via AV,11.
Both values are stored in the product.
If the thermal power limit is surpassed, the MIXIT unit gives a
notification by setting BI,9 to 1.
All limiters can run simultaneously.
ID
Object name R/W
Description
BV,1
Config
Thermal
Power
Limiting ED
R/W
0: Disabled
1: Enabled.
AV,11
Config
Thermal
Power Limit
[kW]
R/W
BI,9
Notification
Thermal
Power High
R
0: Not above
1: Above.
Thermal power is above the limit in
AV,11 for extended time (3600s).
The warning is not resettable but will
reset itself.
7.10.4 Configuring the differential temperature limit
1.
Enable the supply flow by setting BV,3 to 1.
2.
Configure the limit via AV,11.
Both values are stored in the product.
If the differential temperature limit is surpassed, the MIXIT unit gives
a notification by setting BI,9 to 1.
All limiters can run simultaneously.
ID
Object name R/W
Description
BV,3
Config
Primary Delta
T Limiting ED
R/W
0: Disabled
1: Enabled.
AV,13
Config
Primary Delta
T Limit [°C]
R/W
BI,11
Notification
Differential
Temperature
High
R
0: Not above
1: Above.
Primary differential temperature
exceeds the limit in AV,13 for
extended time (3600s). The warning
is not resettable but will reset itself.
7.11 Energy monitor
With the energy monitor function it is possible to monitor the energy
consumption in individual zones. This function does not require any
additional sensors or any additional settings to the system.
The calculated value cannot be used for billing purposes. However,
it is perfect for optimisation purposes in order to prevent excessive
energy costs caused by system imbalances.
Grundfos GO Remote menu:
Main menu
>
Monitoring
>
Heat energy monitor
20