11
Note:
The night-time duty function is deacti-
vated if the selector switch has been set to
speed I, II or III.
6.4 Pump control
During operation, the pump head will be
changed according to the principle "propor-
tional-pressure control". In this control mode,
the pump performance, and consequently the
power consumption, is adjusted to the actual
water requirement.
An example is shown in
s
. In the example, the
pump duty point is changed from (1) to (2) be-
cause of a changed system characteristic
(thermostatic valves are closed) and conse-
quently a lower water requirement.
7. Technical data
Supply voltage:
1 x 230 V –10%/+6%, 50 Hz,
PE.
Motor protection:
The pump requires no exter-
nal motor protection.
Enclosure class:
IP 42.
Insulation class:
F.
Relative air humidity:
Maximum 95%.
Ambient temperature:
0°C to +40°C.
Temperature class:
TF110 to CEN 335-2-51.
Liquid temperature:
+2°C to +110°C.
Pumps in domestic hot-water systems:
+15°C to +60°C.
To avoid condensation in the terminal box and
the stator, the pumped liquid temperature must
always be higher than the ambient tempera-
ture. See the table:
Содержание ALPHA+ 15-40
Страница 1: ...GRUNDFOS ALPHA GRUNDFOS INSTRUCTIONS Installation and operating instructions ...
Страница 2: ...2 ...
Страница 261: ...261 n TM01 8593 0400 o TM01 8594 0400 p TM01 8595 0400 q TM02 0640 0301 ...
Страница 262: ...262 r TM01 8596 0400 s TM01 8597 0400 ...
Страница 263: ...263 t 1 2 3 4 5 6 ...
Страница 264: ...264 u TM02 0634 4900 1 2 ...
Страница 265: ...265 v TM01 8690 0600 1 3 2 ...
Страница 267: ...267 ...
Страница 268: ...268 ...
Страница 269: ...269 ...