background image

 

About this manual 

 

6 | 72 

 

B

A

_

T

D3

-A

M

0

0

1

e

n

_

0

1

4

_

M

X

A

.d

o

cx

 

1.7 

Type plate 

The type plate is located on the front of the filter housing. 

Please specify the data shown on the type plate in order to speed up the processing of your 
inquiries or orders. 

►  Therefore, add the serial number in order to have the necessary data available at 

all times. 

 

 

 

 

Item 

Designation 

Item 

Designation 

Observe operation manual 

DVGW test mark 

EAC mark 

CE mark 

Nominal connection diameter 

Nominal flow 

Nominal pressure 

Max. water temperature 

Max./min. pore size 

10 

QR code 

11 

Product designation 

12 

Data matrix code 

13 

Order no. 

14 

Serial no. 

 

 

●  Product designation:   

 

GENO-backwash filter MXA_______ 

●  Order number: 

 

 

 

 

 

107 ______ 

●  Serial no.: 

 

 

 

 

 

________________ 

 

 

Содержание MXA 1 1/4"

Страница 1: ...We understand water Filter GENO backwash filter MXA 1 MXA DN 100 Operation manual...

Страница 2: ...e written consent of Gr nbeck Wasseraufbereitung GmbH no part of this manual may be reproduced in any way nor may any part be processed duplicated or distributed using electronic systems Non complianc...

Страница 3: ...f supply 18 4 4 Installing the product 19 5 Control unit GENO RS tronic 28 5 1 Components of the control unit 28 5 2 Overview of display 30 5 3 Navigating the control unit 33 5 4 Menu structure 36 5 5...

Страница 4: ...identifies instructions that you must comply with for your own personal safety as well as to avoid damage to property This symbol identifies instructions that you must comply with in order to avoid d...

Страница 5: ...portant 1 First action a first step b second step 2 Second action Result following an instruction Result Lists Listed item Listed sub item Menu paths Status level Menu level Submenu Display texts Disp...

Страница 6: ...rial number in order to have the necessary data available at all times Item Designation Item Designation 1 Observe operation manual 2 DVGW test mark 3 EAC mark 4 CE mark 5 Nominal connection diameter...

Страница 7: ...connected to the power and water supply Comply with the hygiene instructions in chapter 8 Failure to comply can result in microbiological contamination of your drinking water installation Only have pe...

Страница 8: ...ty may occur 2 3 Regulations When installing and starting up the system amongst others comply with the following regulations and guidelines Statutory regulations on environmental protection Provisions...

Страница 9: ...citly designated for a specialist installer Only use this product as intended Make sure that the required inspection and maintenance work is carried out Keep this manual 2 6 Product specific safety in...

Страница 10: ...28 and are intended for installation into drinking water pipes according to DIN EN 806 2 installation immediately downstream of the water meter The filters protect the water pipes and connected water...

Страница 11: ...tion 1 Shock proof plug 1 5 m cable 2 Differential pressure sensor 3 Cover 4 Water meter screw connection 5 Filter housing 6 Pressure gauge 7 Brush 8 Sieve bottom 9 Suction nozzle 10 Filter element 11...

Страница 12: ...d weight the foreign particles stick to the filter element or they fall straight down into the filter funnel The backwash process is activated by the GENO RS tronic control unit and carried out by the...

Страница 13: ...rol unit After several pulses the control unit reverses the direction of rotation and closes the backwash water outlet If the rotary motion is blocked by dirt or wear and tear the control unit detects...

Страница 14: ...1 1 2 DN 65 DN 80 DN 100 50 m filter element 107 052 107 053 107 054 200 m filter element 107 072 107 073 107 074 500 m filter element 107 082 107 083 107 084 Illustration Product Order no Drain conne...

Страница 15: ...stream of distribution pipes or the systems to be protected NOTE Significant temperature differences occurring when the product is moved from one location to another can lead to moisture forming on el...

Страница 16: ...16 72 BA_TD3 AM001en_014_MXA docx GENO backwash filter MXA with screw connections GENO backwash filter MXA with flange connections Item Designation Item Designation 1 Inlet shut off valve 2 Outlet sh...

Страница 17: ...he installation room must provide a floor drain If no floor drain is available an appropriate safety device must be installed in order to prevent water damage We recommend using a protectliQ A The ins...

Страница 18: ...ction with gasket union nut 3 Filter with screw connections 4 Backwash water connection 5 Operation manual 6 Filter with flange connections The filter is available with screw connections for sizes 1 D...

Страница 19: ...ible in horizontal position Free outlet and discharge of the backwash water without backpressure 4 4 1 Changing the direction of flow Check the flow direction given on site If necessary remount the fi...

Страница 20: ...stall the pipe fitting into the pipe the installation dimension must be 190 mm for sizes 1 1 and 206 mm for sizes 1 2 2 Position the filter note the marking for the flow direction on the filter 3 Tigh...

Страница 21: ...ge connection in accordance with DIN EN 1092 1 the distance between the two gaskets must be 220 mm for DN 65 and 250 mm for DN 80 and DN 100 2 Position the filter note the marking for the flow directi...

Страница 22: ...ckwash water can be collected in a bucket container Install a waste water pipe not included in the scope of supply at the pre installed drain connection with free outlet Item Designation Item Designat...

Страница 23: ...stall a waste water pipe towards the drain connection The backwash water connection is installed The drain connection is available as an option refer to Accessories chapter 3 5 To install the drain co...

Страница 24: ...on the electrical system Make sure that the mains voltage is disconnected and that the plug is unplugged Do not connect to mains until the connection work has been completed and the control unit is cl...

Страница 25: ...wall NOTE Securely fasten the control unit Precarious and unsound fastening can cause the control unit to crash Prior to fastening the control unit check the wall type present Select fasteners on site...

Страница 26: ...al pressure switch Q Backwash signal H Do not connect wire 3 R Collective fault signal active contact rating 250 VAC 3A each I Programmable input M Mains 230 VAC 50 Hz J Cam operated switch T System f...

Страница 27: ...r Er 3 or Er 5 active No backwash lock active Backwash lock at external input As an alternative the input can be used for an external backwash lock refer to chapter 5 5 1 Parameter d Combined operatio...

Страница 28: ...3 Operating Menu level 4 Release button 5 Connection level NOTE Incorrect setting operation of the control unit Dangerous operating conditions functional impairments may occur health personal property...

Страница 29: ...ial pressure evaluation can be deactivated 3 Activation by external signal The backwash can be triggered by means of an external voltage free contact If the contact is closed for more than 1 second a...

Страница 30: ...A docx 5 2 Overview of display Item Designation Item Designation 1 Display 2 Connection data of the control unit 3 Button I for information 4 Button R for backwash 5 Button P for program 6 Explanation...

Страница 31: ...h lock is active Differential pressure Indicates a differential pressure controlled backwash Statically when the differential pressure evaluation is activated Flashing when a backwash triggered by dif...

Страница 32: ...ckwash and backwash after acknowledgement of an error A flashes during automatic backwash 5 minutes before and at the end of an off period E flashes if the programmable input is set as backwash lock a...

Страница 33: ...mode Switches to User menu level In the User menu level Opens parameters Saves the settings and closes parameters Backwash Button R In standard mode Starts the manual backwash In the User menu level S...

Страница 34: ...level Press the buttons and in the status level at the same time for more than 1 s The display switches from the time to three flashing digits 000 and the parameter no changes to C 1 Press the or the...

Страница 35: ...ou want to exit the setting of the open parameter without making any changes Press the and the button at the same time The parameter will be closed and the unchanged value is displayed continuously Sa...

Страница 36: ...ng Factory settings Setting range 0 Evaluation of the differential pressure signal The GENO RS tronic utilises the differential pressure switch to detect independently when a backwash is required 1 0...

Страница 37: ...ervice company 1 0 Maintenance work is carried out by the owner user 1 Maintenance work is carried out by Gr nbeck s technical service authorised service company A Acknowledgement of maintenance The o...

Страница 38: ...MXA is open Close the open drain outlet for 1 5 min 1 Press and hold the button 2 Plug the mains plug into the socket 3 Release the button NOTE Faulty connection installation Filter is not closing or...

Страница 39: ...ream of the filter to the maximum 5 Apply the maximum operating pressure The filter is vented 6 Check the filter for tightness 7 Carry out a backwash The filter is in operation 6 3 Handing over the pr...

Страница 40: ...is active Time until the next maintenance and or the remaining number of backwash processes until the next maintenance Time stored 7 1 1 Retrieving information Status level Information level Press the...

Страница 41: ...is only updated during the ongoing backwash XX Upon opening factory setting 36 YY Upon closing factory setting 34 40 6x XX XX Display is reset to basic display time 7 2 Setting parameters in the User...

Страница 42: ...he button to set desired value 7 Press the button to save the setting The current time is set 7 2 2 Starting a backwash manually Status level Press and hold the button for more than 5 s A manual backw...

Страница 43: ...The display switches from the time to the three flashing digits 000 and the parameter no switches to C 1 Press the or the button to select code 113 6 Press the button to confirm the selection 7 3 2 Ev...

Страница 44: ...very d days and in the next menu h hours Setting the backwash interval 1 Press the button to switch to parameter 1 In the factory setting the following is displayed 1 for the selected parameter The va...

Страница 45: ...he desired value of the parameter 8 Press the button to save the value The value of the parameter stops flashing The hours are set Press the and the button at the same time to return to the status lev...

Страница 46: ...ract ensures that all the required maintenance work will be performed in due time Only use genuine spare and wearing parts from Gr nbeck 8 1 Cleaning WARNING Damp cleaning of live components Risk of e...

Страница 47: ...ed changing filter element gaskets suction nozzle unit 8 3 Inspection According to DIN EN 806 5 the owner user must inspect the filters every 2 months 1 Check the installation for leaks 2 Open several...

Страница 48: ...Health risk due to contamination of the drinking water Observe the intervals for inspection and backwash of the filter element 8 4 1 Semi annual maintenance Manual backwash of the filter During the b...

Страница 49: ...er Refer to technical service manual TD4 AM001 for GENO backwash filter MXA 8 4 2 Annual maintenance Carrying out annual maintenance work requires specialist knowledge This kind of maintenance work ma...

Страница 50: ...ion nozzle stops in its position and the water can flow out of the filter 4 Unscrew the filter funnel turn anti clockwise 5 Unscrew the lower suction nozzle from the pipe nozzle 6 Remove the sieve bot...

Страница 51: ...11 Check the O rings of the filter element outside and inside for wear and tear Depending on the filter size different filter elements are combined If one filter element is damaged you can either rep...

Страница 52: ...sition the sieve bottom between the pipe nozzle and the lower suction nozzle 3 Screw the lower suction nozzle onto the pipe nozzle until the O ring is just not visible any longer 4 Slide the filter fu...

Страница 53: ...e sizes 50 m 200 m and 500 m only after consultation with Gr nbeck Wasseraufbereitung GmbH refer to accessories on page 14 Designation Order no 1 1 1 2 DN 65 DN 80 DN 100 100 m filter element 107 061...

Страница 54: ...low contact Gr nbeck s technical service authorised service company Have your system data refer to chapter 1 7 handy Troubleshooting may only be carried out by a specialist installer Refer to technica...

Страница 55: ...pulses from the microswitch Contact the specialist installer or Gr nbeck s technical service If water leaks from the drain opening close the filter manually Rubber gasket for backwash water outlet has...

Страница 56: ...ntact the specialist installer or Gr nbeck s technical service Er 5 Differential pressure sensor or its connection line defective Contact the specialist installer or Gr nbeck s technical service Have...

Страница 57: ...not rotate or is buzzing only Wiring error terminals 10 21 in the RS tronic or connecting terminals at the motor s mounting plate Check the wiring according to the wiring diagram Motor or control uni...

Страница 58: ...Gasket at the lower suction nozzle defective or worn Check the gasket of the drain nozzle and replace the suction nozzle unit if required Motor does not rotate or runs sluggish Mechanical blockage in...

Страница 59: ...Due to malfunctions it may be necessary to close the filter s suction nozzle manually to avoid unnecessary water leakage To do so you will need the following Open ended wrench SW11 or Flat head screw...

Страница 60: ...72 BA_TD3 AM001en_014_MXA docx 3 Loosen the nuts of the cover 4 Lift the cover of the filter housing 5 Disconnect the cables of the microswitch You can now dismount the motor 6 Lift the motor unit off...

Страница 61: ...ff valves The water no longer escapes Mount the drive unit in reverse order NOTE The filter s suction nozzle has been tightened too much The lower suction nozzle got stuck The drive unit does not prov...

Страница 62: ...duct or the electrical and electronic components must not be disposed with household waste Dispose of electrical and electronic products and components in an environmentally sound manner Learn about t...

Страница 63: ...he filter element mm 100 100 min 100 optimum from 215 Length of cable for differential pressure sensor mm 1500 Length of cable for drive unit mm 1500 Length of mains cable mm 1500 Empty weight with co...

Страница 64: ...160 180 J Max sealing surface mm 122 140 158 K Number of M 16 screws pcs 4 8 8 Length of cable for differential pressure sensor mm 1500 Length of cable for drive unit mm 1500 Length of mains cable mm...

Страница 65: ...curves Pressure loss curves of GENO backwash filters MXA 1 and 1 Item Designation Item Designation 1 Pressure difference bar 2 Flow rate m3 h Pressure loss curves of GENO backwash filters MXA 1 and 2...

Страница 66: ...XA DN 65 DN 80 and DN 100 Item Designation Item Designation 1 Pressure difference bar 2 Flow rate m3 h Consumption data Backwash water volume at a water pressure of 3 bar and a backwash time of 1 5 mi...

Страница 67: ...onnection acc to DIN EN 1717 yes no Floor drain available yes no Safety device yes no Operating values Water pressure at raw water inlet bar Water pressure downstream of pressure reducer bar Residenti...

Страница 68: ...Operation log 68 72 BA_TD3 AM001en_014_MXA docx 12 2 Maintenance Date Work performed Signature...

Страница 69: ...The afore mentioned system also complies with the following directives and provisions Directive on the Restriction of Hazardous Substances RoHS 2011 65 EU Furthermore we confirm compliance with the es...

Страница 70: ...16 Installation example MXA with screw connections 16 Installing the flushing water connection 22 Intervals 47 M Menu structure 36 Messages on the display 54 Mounting MXA with flange connection 21 Mo...

Страница 71: ......

Страница 72: ...Gr nbeck Wasseraufbereitung GmbH Josef Gr nbeck Str 1 89420 Hoechstaedt Germany For more information go to www gruenbeck com 49 9074 41 0 49 9074 41 100 info gruenbeck com www gruenbeck com...

Отзывы: