6.2 Intervals
Grünbeck recommends a semi-annual and an annual
maintenance according to DIN EN 806-5.
Operation
Interval
Execution
Inspection
2 months
Visual/function test, read off pressure (with
BOXER KDX)
Maintenance
6 months
Replace filter cartridge, clean support fabric,
adjust maintenance ring
Annually
Check O-rings/flat gaskets for wear, check tight
fit, replace filter cartridge
Maintenance
5 years
Recommended: Support fabric, change seals.
10 years
Recommended: in addition to 5-year interval
–
replace filter cylinder.
6.3 Inspection
► Check the installation for leaks and function.
► Read off the pressure (for BOXER KDX). Replace the filter
cartridge in case of contamination and/or increased
differential pressure.
6.4 Maintenance
WARNING:
Filter cartridge not replaced regularly. Uncleaned
support fabric.
● Health risk due to contamination of the drinking water.
► Observe the intervals for inspection and replacement of
the filter cartridge (according to DIN EN 806-5 every 6
months at the latest).
► Discard a used filter cartridge.