ARK 5.1-25.6XH-A1 High Voltage Battery System

                    

                             

User Manual (V1.0)

  

                       

4-13/F,Building A,Sino-German(Europe) Industrial Park,

Hangcheng Ave,Bao’an District, Shenzhen, China

Содержание ARK 5.1-25.6XH-A1

Страница 1: ...w Energy Co Ltd 86 755 2747 1942 www ginverter com T E W service ginverter com GR UM 242 A 00 ARK 5 1 25 6XH A1 High Voltage Battery System User Manual V1 0 4 13 F Building A Sino German Europe Indust...

Страница 2: ...rements 4 2 Installation Required Tools 4 3 Installation Procedures 4 4 Electrical Connection About this Document This document describes the installation electrical connection operation commission ma...

Страница 3: ...duct is shown as below Fig 1 2 Schematic diagram of power panel Location Port Function 1 POWER Wake up battery 2 INV Port for communication with hybrid inverter 3 Link in Battery system in parallel co...

Страница 4: ...ery management units power and signal terminals and mechanical parts Compared with other battery systems it has better charging and discharging performance higher charging and discharging efficiency m...

Страница 5: ...with liquids Safety 2 2 2 2 Operation Precautions Do not touch the battery system with wet hands Do not disassemble the battery system without permission Do not crush drop or pierce the battery pack...

Страница 6: ...u touch the leaking electrolyte do as below immediately Inhalation Evacuate the contaminated area and seek medical help Eye contact Rinse eyes with flowing water for 15 minutes and seek medical help S...

Страница 7: ...l damages Prohibit to pile up more than six battery pack There will be a drop in capacity during transportation and storage Transportation temperature is between 20 C to 45 C relative humidity 5 95 RH...

Страница 8: ...system Drill Screw Driver Wrench Pencil Tap Measure Multimeter It is recommended to wear the following safety gear when dealing with the battery system Insulated Glove Safety Goggle Safety Shoes 4 3...

Страница 9: ...s a row only one battery base is required and two rows are required two And the wall bracket is only used for wall installation The number of wall brackets are determined by the number of battery modu...

Страница 10: ...Fig 4 9 Multiple battery installation process with wall mount 4 3 3 Floor Standing Installation Step 1 Choose an alloy drill with a diameter of 8mm and drill at least 50mm mounting holes on the wall C...

Страница 11: ...nts front view Pin assignments front view BDC 95045 A1 communication interface MOD TL3 XH Hybrid inverter three phase interface Silk screen Terminal serial number Definition Silk screen Terminal seria...

Страница 12: ...onnect the ommunication plug of the last battery pack otherwise it will cause system failure Note 4 4 2 2 Electrical wiring connection A BDC 95045 A1 High voltage controller wiring Step 1 Insert the p...

Страница 13: ...ration Please stand on dry insulating objects and do not wear conductive material such as watches and necklace during operation Insulated tools should be used Do not contact any positions with potenti...

Страница 14: ...ransport the battery pack or High voltage controller to the designated repair site Install new battery pack or High voltage controller based on procedure specified in Section 4 6 3 System Failure Info...

Страница 15: ...ller to repair battery Technical Specifications7 7 1 ARK XH A1 high voltage system System Model ARK 5 1XH A1 ARK 7 6XH A1 ARK 10 2XH A1 ARK 12 8XH A1 ARK 15 3XH A1 High Voltage Controller Model BDC 95...

Страница 16: ...tage battery packs Voltage after series Single phase power conversion system allows 2 7PCS battery modules in series its nominal voltage is 400V Three phase power conversion system allows 3 10PCS batt...

Страница 17: ...ging to 650V of DC DC output Module side voltage and current is limited by DC DC circuit ARK 20 4XH A1 IFpP 41 150 102 1P16S 8S M 10 50 90 constant current 15A charging to 650V of DC DC output Module...

Страница 18: ...licker green Protection Charge and discharge Over current hardware protection SOC indicates current remaining capacity t 1S RUN ALM light flicker green Ambient temperatur e over temperatur e alarm t 1...

Страница 19: ...ilure protection t 1S RUN ALM light flicker red Main circuit failure protection t 1S RUN ALM light flicker red EEPROM fault protection t 1S RUN ALM light flicker red Front end chip failure protection...