08.04.2021
11 / 116
CONDENSINOX -
Installation, Use and Maintenance
Categories
CH-ES-GB-EI-PT-IT-AT CZ-HU-SK-LT-NO-AT-LV-DK-EE-FI-GR-
RO-SE-SI
CONDENSINOX
40-60 kW
B23 - B23 P
II
2H3P
I
2H
C13 - C33 - C53
C43 - C83
I
2H
I
2H
CONDENSINOX
50 kW
B23 - B23 P
I
2H
CONDENSINOX
80-100 kW
B23 - B23 P
II
2H3P
I
2H
C13 - C33 - C53
C43 - C83
I
2H
I
2H
2.4. Gas supply pressures
INFORMATION:
The pressures given below should be measured at the input to the
gas valve.
H G20
natural gas
L G25
natural gas
G31 propane
(only with B23 and B23P)
Nominal pressure (mbar)
20
25
37
Minimum pressure (mbar)
17
20
25
Maximum pressure (mbar)
25
30
45