2.4
External Current Sensor
The DGF100 can work with an external CS, which is useful in the situation where the cables together are
bigger than the 46 mm of the internal CS opening allows, or when higher than 660V system voltages are
needed.
for the available options and
2.5
Frame Bonding/Chassis Ground
Chassis ground is the ground to which all of the non-current carrying metal equipment is
connected/bonded.
In order to meet the Electromagnetic Compatibility (EMC) requirements a firm and short connection is
required between terminal FB and the chassis ground point. The chassis ground must not be more than
50 mm away from the unit.
If the DGF100 is mounted on a 35 mm DIN rail, a ‘DIN rail ground terminal block’ can be installed beside
the unit to act as the chassis ground point. Use a 2-2,5 mm
2
(14 AWG) stranded conductor.