reference
manual, rev 1, Feb 22, 2022
Ground
Fault
Systems
B.V.
8.
T
ABLES AND FIGURES
8.1
Table 1 - Dipswitch settings
‘D’ denotes down and ‘U’ denotes up.
Values are primary currents for a 500:1 ratio internal or external Current Sensor.
For other ratio’s see
Switch no.
Function
Set
to
Meaning
1
CT configuration D ♦
U
No interposing CT,
With 500:1 External CS,
or with 5000:5 interposing CT
With 500:5 interposing CT
2 3 4 5
Ground Fault
Trip level
D D D D ♦
D D D U
D D U D
D D U U
D U D D
D U D U
D U U D
D U U U
U D D D
U D D U
U D U D
U D U U
U U D D
U U D U
0,030 A
0,040 A
0,060 A
0,090 A
0,150 A
0,250 A
0,40 A
0,60 A
0,90 A
1,50 A
2,50 A
4,00 A
6,00 A
9,00 A
6 7 8
Ground Fault
Trip Delay time
D D D ♦
D D U
D U D
D U U
U D D
U D U
U U D
U U U
20
ms
50
ms
100
ms
200
ms
500
ms
1000
ms
2000
ms
5000
ms
9 10
Operation Mode D D ♦
D U
U D
U U
Continuous Non-Failsafe operation
Continuous Failsafe operation
Pulsed Auto Reset operation (Pulse turns
off 3 sec after G/F removed)
Pulsed Non-Failsafe operation
♦ Factory settings