Quick Start Guide

Single/Three Phase Vari-Green

®

 Motor

Vari-Green Motor Quick Start Guide

When delivered, the Vari-Green Motor is pre-
programed to run from either an on-board dial or a 
0-10 VDC control signal. A 0-1.99 Volt control signal 
will be received as a “stand-by” command.
A run command is acknowledged, as well as a 
speed reference from 2-10 V.
For more information about this 
Vari-Green Motor, please review 
the Installation, Operation and 
Maintenance Manual found by 
following this QR code:

www.greenheck.com/vari-green/vari-green-motors

Step 1

Connect the power supply. Verify Input Voltage and 
phase matches nameplate of motor/drive.

THREE PHASE

L1

L2

L3

L1

L2

L3

L1

L2

L3

L

N

DISCONNECT

POWER

DISCONNECT

POWER

SINGLE PHASE

THREE PHASE

L1

L2

L3

L1

L2

L3

L1

L2

L3

L

N

DISCONNECT

POWER

DISCONNECT

POWER

SINGLE PHASE

Step 2

Connect control wiring to the control terminal.

DIAL ON-BOARD

RED

WHITE

BLACK

*JUMPER

+24V, 100mA

D1, ENABLE

2D

D3/A2

+10VDC

A1

COMMON

AO/DO OUTPUT

COMMON

MODBUS RTU–

MODBUS RTU+

+24V, 100mA

D1, ENABLE

2D

D3/A2

+10VDC

A1

COMMON

AO/DO OUTPUT

COMMON

MODBUS RTU–

MODBUS RTU+

RED
WHITE

0-10V CONTROL SIGNAL

*JUMPER

COMMON

0-10VDC CONTROL

NOTE:

 Factory default settings:

1.  Terminal 2 is set as an ENABLE command. From the 

factory there is a jumper from terminal 1 to 2. A START/
STOP switch can be used between these terminals to 
ENABLE/DISABLE the drive.

2.  When this Vari-Green Motor is ordered in a 0-10 VDC 

Control configuration, the motor is shipped with a jumper 
between terminal 5 and 6. This will run the motor at full 
speed when power is connected. Remove this jumper 
before landing 0-10 VDC control wires. 

Step 3

Install motorized backdraft damper wiring, if 
applicable. The relay RL-1 is set from the factory to 
close when a run command is given.

(DAMPER POWER SOURCE)

N

LINE

MOTORIZED DAMPER

RL–1A

RELAY COMMON

RL–1B

RELAY N.O. COMMON

250VAC, 6A

30VDC, 5A

Step 4

Apply power to unit. If a control signal 
is present, the RL-1 relay will close and 
the motor will ramp up to the 
referenced speed. If a jumper is 
installed between terminals 5 and 6, 
the motor will go to 100%.

Step 5

Balance the fan. Whether changing the position of 
the on-board dial or adjusting the control voltage, 
the fans speed can be set from the minimum to the 
motor’s factory programmed maximum speed.  
Re-apply the motor cover. 