Model SMDR-501 meets the requirements for 

smoke dampers established by:

National Fire Protection Association 

 

NFPA Standards 92A, 92B, 101 & 105

IBC   International Building Codes
New York City 

(MEA listing #260-91-M)

California State Fire Marshall

 

Listing #: 2330-0981:104

Application

Model SMDR-501 is a round smoke damper with extremely low 
leakage. The SMDR-501 has been qualified to 3,000 fpm (15.2 m/s) 
and 4 in. wg (1.0 kPa) for operational closure in emergency smoke 
control situations, for use in HVAC system applications.

Ratings

 

Leakage:

   Class I 

 

Pressure:

   4 in. wg (1.0 kPa) - differential pressure 

 

Maximum Velocity:

  3000 fpm (15.2 m/s) 

 

Temperature:

   350°F (177ºC) depending on the actuator.

Standard Construction

 

Frame/sleeve:

   20 ga. (1mm) galvanized steel round integral 

 

  sleeve 

 

Blades:

  Double skin galvanized steel (14 ga. [2mm] 

 

  equivalent) round style blades 

 

Seals:

  Silicone rubber. 

 

Axles:

 

1

2

 in. (13mm) dia. plated steel. 

 

Bearings:

  Oil impregnated stainless steel

Size Limitations:

 

Minimum Size:

  6 in. diameter (152mm) 

 

Maximum Size:

   24 in. diameter (610mm)

Optional Features:

•  Electric or pneumatic actuators to accomplish smoke 

management and system functions.

•  Open/Close Indicator (OCI) for remote indication of blade 

position.

• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve

SMDR-501

Smoke Dampers

 

UL 555S Leakage Class I

* D dimension furnished approximately 

1

8

 in. (3mm) undersize.

“UL CLASSIFIED (see complete marking on 

product)”

“UL CLASSIFIED to Canadian safety standards 

(see complete marking on product)”

 

Standard 555S (Listing #R13317)

Specifications

True Round Smoke Dampers meeting the following specifications 
shall be furnished and installed where shown on plans and/or as 
described in schedules. Dampers shall meet the requirements of the 
latest edition of NFPA 92A, 92B, 101 & 105. 

Dampers shall be tested, rated and labeled in accordance with the 
latest edition of UL Standards 555S. Dampers shall be UL labeled for 
use in dynamic systems. The damper shall have a dynamic closure 
airflow rating equal to or greater than the airflow at the damper’s 
installed location and a dynamic closure pressure rating of 4 in. wg 
(1kPa).

Dampers shall have a UL 555S leakage rating of Class I and a 
temperature rating of 250º F (121ºC) minimum. Dampers shall have a 
UL555S operational airflow rating equal to or greater than the airflow 
at its installed location and an operational pressure rating of 4 in. wg 
(1 kPa). Damper actuators shall be factory mounted and qualified for 
use with the damper in accordance with UL555S. 

Damper actuators shall be (specified select one of the following) 
electric type for 120 (or 24) volt operation or pneumatic type for 25 psi 
minimum operation (30 psi maximum). Manufacturer’s submittal data 
shall indicate actuator space requirements around the damper. 

All UL555S operational ratings and leakage ratings shall be qualified 
for airflow and pressure in either direction through the damper. UL 
ratings shall allow for mounting damper vertically or horizontally. 

The Damper Manufacturer’s submittal data shall certify all air 
performance pressure drop data is licensed in accordance with the 
AMCA certified ratings program for test figures 5.2, 5.3, and 5.5. 
Damper air performance data shall be developed in accordance with 
the latest edition of AMCA Standard 
500-D. 

Basis of design is Greenheck’s model SMDR-501.

Copyright © 2008 Greenheck Fan Corporation

SMDR-501 Rev. 7 June 2008

D*

Installation instructions available at www.greenheck.com.