Inline grease exhaust fans are excellent alternative for kitchen applications when roof or wall mounted ventilators 
are not practical. The TCB with UL 76 grease option is designed to withstand the demands of high temperature 
kitchen grease exhaust and high-pressure duct washes.

Continuously welded housing and integral duct flanges 
provide air and water tight design.
Bearing cover gasketed and includes a labyrinth shaft seal 
to prevent moisture leakage during normal operation and 
while cleaning with high pressure solvents.
Continuously welded belt tube keeps the belts and 
bearings clean.
Two threaded drain connections are located 90° from the 
motor location to allow for removal of grease and moisture.

UL 76 is concerned with fans 
designed for removal of smoke and 
grease laden vapors with airstream 
temperatures up to 300°F.
•  Meets all UL 705 Requirements
•  Bolted Access Door
•  Drain Connection
•  Meets requirements of NFPA 96
   Ventilation Control and Fire 

Protection of Commercial  
Cooking Operations

Listed Power 
Ventilation for 
Restaurant 
Exhaust 
Appliances 
13G3 
Maximum 
Operating 
Temperature 
300°F.

The TCB inline grease fan is tough to beat when 
packaged with our full line of kitchen hoods and grease 
extraction options. Take advantage of Greenheck’s 
expertise in providing a total solution in kitchen 
ventilation equipment.

A Tough Package to Beat

Leak Resistant Construction Features

Inline grease exhaust fans should be installed near the end of the duct run to reduce sound at the hood.
Inline fan must be securely bolted to the exhaust duct per NFPA-96 guidelines. Greenheck’s companion flanges 
are recommended for ease of installation.
Grease exhaust fans and ductwork must maintain 18 inches (46 cm) minimum clearance to combustible 
material. If the ductwork and fan are insulated, the inspection door must be accessible for maintenance.
A minimum of 10 ft. (3.0 m) of clearance must be kept from the fan outlet to adjacent buildings, property lines, 
or the closest point of any air intake or operable window at or below the plane of the exhaust termination.
Greenheck recommends that all inline grease applications be reviewed by your local code official to ensure 
compliance with NFPA, IMC, and other local codes.


System Design Guidelines

1

2

3

4

5

6

7

Mounting and Serviceability Features

4

6

7

5

1

2

3

4

Optional Construction for

UL 762 Restaurant Exhaust

Universal mounting brackets allow for rotation of the motor to 
the 3 or 9 o’clock position at the jobsite.
Duct flanges and access door bolt locations are no more
than 4 inches (100 mm) on center per NFPA 96.
“Easy Access Door” provides access for duct cleaning and allows removal of the wheel, 
shaft and bearings for maintenance. Gasket is rated for 400° F (00° C) and prevents 
leakage during operation.

Airflow

Duct to heat source

Ambient temperature 

not to exceed 120ºF

Wall and/or ceiling should enclose 

fan when used for emergency heat 

and smoke exhaust. Enclosure shall

be per NFPA 96 or local building codes.

Roof

Cooling air for 

drives and 

bearings

Minimum duct 

at discharge

To building

exterior