Pressure Drop Data 

SEFSD-211

This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations shown. All 

data has been corrected to represent standard air at a density of .075 lb/ft

3

 (1.201 kg/m

3

).

Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along with an 

analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a given HVAC 

system.

AMCA Test Figures

Figure 5.3

 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test configurations 

because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper. 

Figure 5.2

 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop than 

Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.

Figure 5.5

 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely high 

entrance and exit losses due to the sudden changes of area in the system.

5D

6D

5D

D

4 (W) (H)

3.14

Содержание Stainless Steel 3V Blades SEFSD-211

Страница 1: ...eel jamb seals Linkage 316 stainless steel concealed in jamb Axles 1 2 in 13mm diameter 316 stainless steel Bearings 316 stainless steel sleeve type Closure Device 165º F 74ºC RRL Size Limitations Minimum Size 8 in W x 6 in H 203mm W x 152mm H Maximum Size Single Section 24 in W x 30 in H Horizontal or Vertical Mount 610mm W x 762mm H or 22 in W x 36 in H Vertical Mount 559mm x 914mm Multiple Sect...

Страница 2: ...ystem AMCA Test Figures Figure 5 3 Illustrates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because en...

Страница 3: ...ssureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 04 500 0 02 500 0 01 500 0 01 1000 0 14 1000 0 07 1000 0 04 1000 0 06 1500 0 31 1500 0 16 1500 0 09 1500 0 13 2000 0 55 2000 0 29 2000 0 16 2000 0 23 2500 0 86 2500 0 45 2500 0 25 2500 0 36 3000 1 24 3000 0 65 3000 0 36 3000 0 52 3500 1 69 3500 0 89 3500 0 49 3500 0 70 4000 2 20 40...

Страница 4: ...00 0 48 3500 0 33 3500 0 53 4000 1 44 4000 0 63 4000 0 42 4000 0 70 12in x12in 305mm x 305mm 24in x24in 610mm x 610mm 36in x36in 914mm x 914mm 12in x48in 305mm x 1219mm Velocity fpm Pressure Drop in wg 500 0 02 1000 0 07 1500 0 16 2000 0 29 2500 0 45 3000 0 64 3500 0 88 4000 1 14 48 in x 12 in 1219mm x 305mm R Greenheck Fan Corporation certifies that the model SEFSD 211 shown herein is licensed to...

Страница 5: ...fpm PressureDrop in wg Velocity fpm PressureDrop in wg Velocity fpm PressureDrop in wg 500 0 06 500 0 03 500 0 03 500 0 03 1000 0 22 1000 0 14 1000 0 12 1000 0 13 1500 0 50 1500 0 31 1500 0 26 1500 0 30 2000 0 89 2000 0 54 2000 0 46 2000 0 53 2500 1 39 2500 0 85 2500 0 73 2500 0 83 3000 2 00 3000 1 22 3000 1 05 3000 1 19 3500 2 72 3500 1 66 3500 1 42 3500 1 62 4000 3 55 4000 2 17 4000 1 86 4000 2 ...

Страница 6: ...OR 12 305 12 305 Actuators and Accessories Space Envelopes Externally mounted actuators always require space out side of the damper sleeve The S dimension illustrates the clearance required for various available actuators On dampers less than 18 in 457mm high actuators may also require clearances above and or below the sleeve B and T dimensions are worst case clearance require ments for some dampe...

Страница 7: ...perature rating of 250 F 121 C minimum and shall be operational and dynamic rated to operate at maximum design air flow at its installed location Each damper shall be supplied with an appropriate actuator installed by the damper manufacturer at the time of damper fabrication Damper actuator shall be specifier select one of the following electric type for 120 24 or 230 volt operation or pneumatic t...

Отзывы: