Greenheck SSFD-150 Скачать руководство пользователя страница 1

Installation instructions available at www.greenheck.com

®

Optional Features

• Sealed transitions (sleeve required) and sleeves
• Security Bars
• One piece retaining angles (POC)
• Transitions (B, B2, C, CO, CR, R)

Installation

All fire damper installations require the use of sleeves, angles and methods described in Greenheck Fire Damper 
Installation Instructions. Sleeves can be field fabricated or factory furnished as a complete damper/sleeve 
assembly.

Construction

Standard

Optional

Frame Material

304SS*

-

Frame Depth

11

16

 in.

(94mm)

-

Blade Material

304SS*

-

Closure Spring

Stainless Steel

-

Fusible Link

165°F (74°C)

212°F or 286°F

(100°C) or (141°C) 

Mounting

Vertical

Horizontal

* in gauges required by UL listing R-13317

Model SSFD-150

Static Rated Fire Dampers

1

1

2

 Hour Fire Resistance Rating

Application

Model SSFD-150 is a static rated fire damper approved for 
use in walls and partitions with fire resistance ratings less 
than 3 hours. This model carries a 1

1

2

 hour UL fire damper 

label. UL555 classifies static rated fire dampers for use 
in HVAC systems that are automatically shut down in the 
event of fire. SSFD-150 is contructed out of 304 stainless 
steel.

Ratings

UL555 Fire Resistance Rating

 

Fire Rating:

 1

1

2

 hours

Model SSFD-150 meets the requirements for fire damper 
established by:

National Fire Protection Association

(NFPA Standards 80, 90A & 101)

Underwriters Laboratories Standard 555 

(Listing #R13317)

IBC International Building Codes
New York City 

(MEA listing #260-91-M)

California State Fire Marshall

(Listing #3225-981:102)

“K” side

W*

H*

Vertical Mount

Horizontal Mount

Stainless Steel
Closure Spring

3 11/16 in.
(94mm)

Fusible Link (replaceable)

See complete marking on 
product.
UL 555 Classification 
R13317

* These dimension are furnished approximately 

1

4

 in. (6mm) undersize.

Отзывы: