13
Model PV
e
Heat Recovery Unit
MODULATING CONTROL FOR FAN SPEED
(0-10 VDC)
Parameter
Setting
V1000
J1000
A1-01
Access Level
2
2
b1-17
VFD Start-Up Setting
1
1
C1-01
Acceleration Time
30 sec.
30 sec.
C1-02
Deceleration Time
30 sec.
30 sec.
C6-02
Carrier Frequency
1
1
d2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
Motor
FLA
Motor
FLA
H3-04
Terminal A1 Bias
50%
50%
A1-01
Access Level
0
0
MULTISPEED CONTROL FOR FAN SPEED
(1/3 OR 1/2 SPEED REDUCTION)
Parameter
Setting
V1000
J1000
A1-01
Access Level
2
2
b1-01
Reference Source (Frequency)
0
0
b1-17
VFD Start-Up Setting
1
1
C1-01
Acceleration Time
30 sec.
30 sec.
C1-02
Deceleration Time
30 sec.
30 sec.
C6-02
Carrier Frequency
1
1
d1-01
Frequency Reference 1
60 Hz
60 Hz
d1-02
Frequency Reference 2
40 Hz
40 Hz
d1-03
Frequency Reference 3
30 Hz
30 Hz
d1-04
Frequency Reference 4
60 Hz
60 Hz
d2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
Motor
FLA
Motor
FLA
H1-04
Multfunction Input Sel 4
(Terminal S4)
3
3
H1-05
Multifunction Input Sel 5
(Terminal S5)
4
4
H1-06
Multifunction Input Sel 6
(Terminal S6)
5
NA
H3-10
A2 Not Used
F
NA
A1-01
Access Level
0
0
CO2 SENSOR CONTROL FOR FAN SPEED
(1/2 SPEED WHEN C02 DROPS bELOW 700 PPM)
(FULL SPEED WHEN C02 RISES AbOVE 800 PPM)
Parameter
Setting
V1000
J1000
A1-01
Access Level
2
2
b1-01
Reference Source (Frequency)
0
0
b1-17
VFD Start-Up Setting
1
1
C1-01
Acceleration Time
30 sec.
30 sec.
C1-02
Deceleration Time
30 sec.
30 sec.
C6-02
Carrier Frequency
1
1
d1-01
Frequency Reference 1
60 Hz
30 Hz
d1-02
Frequency Reference 2
30 Hz
60 Hz
d2-02
Ref Lower Limit
50%
50%
E2-01
Motor Rated FLA
Motor
FLA
Motor
FLA
H3-10
A2 Not Used
F
NA
A1-01
Access Level
0
0
Factory Set Points -
continued
Resetting the V1000 drive to factory defaults
To reset the V1000 drive back to Greenheck factory
defaults go to parameter A1-01 and set it to “2”.
Then go to A1-03 and change it to “1110” and press
enter. The drive is now reset back to the settings
programmed at Greenheck. This option is not
available on the J1000.