background image

Inserting Damper into Wall/Floor Openings

Figures 5 - 7

 show installations for grille access and continuing duct applications.

The following maximum distances outside the barrier apply: 
  • Steel stud and masonry barriers:
    - 8

1

2

 in. (216 mm) provided the width and height of the damper are both 24 in. (610 mm) or less and the  

    damper sleeve is 20 gauge 
  - 7

1

2

 in. (191 mm) in all other instances

  • Wood stud walls: 6

1

2

 in. (165 mm)

To provide "through the grille" access to the damper actuator, the damper is located toward the back of the sleeve 
and the actuator is installed between the damper and grille. Actuator and damper can be accessed and serviced by 
removing the grille. To provide access to the damper actuator for continuing ductwork, refer to the requirements of 
NFPA 90A.

Figure 7: Continuing Duct - Horizontal or Vertical Mount

Figure 5: Through the Grille Access - Duct Terminates 

Metal Stud

Wooden Stud Construction

Gypsum Wallboard 

Stud or Runner

Retaining 
Angle 

(Duct Terminates)

In wood stud construction, 
gypsum wallboard must cover
all wood stud surfaces.

Grille 

(Supplied 

by others)

Factory Supplied 
Thermal Blanket

Fire damper or 
combination fire 
smoke damper 

6 1/2 in. 

Max. 

#10 sheet metal 
screws, 2 1/2 inches 
long,  spaced 6 in. on 
center and maximum 
of 2 in. from corners 
(minimum of 2 screws 
per side). Screw into 
rear portion of the 
studs so as to avoid 
space conflicts with 
the grille assembly.

Figure 6: Through the Grille Access - Duct Terminates 

Wood Stud

Factory Supplied 
Thermal Blanket

7 1/2 in. max. or
8 1/2 in. max.*

Damper 

Masonry 
floor

Steel stud

Flange 

Grille 

(Supplied 

by others)

Factory Supplied 
Thermal Blanket

7 1/2 in. Max.

or

8 1/2 in. Max.*

Damper 

#10 2 1/2 in. long sheet metal 
screws spaced 6 in. on center and 
maximum of 2 in. from the corners 
(minimum of 2 screws per side) 
through the sleeve into the header, 
sill and jamb framing members. 
Screw into rear portion of the 
studs so as to avoid space 
conflicts with the grille assembly.

*  

The out of wall/floor limitation for 
steel stud and masonry barriers 
is 7

1

2

 in. (191 mm) except in 

instances where both the width 
and height of the damper is 24 
in. (610 mm) or less and when 
the damper sleeve is 20 gauge in 
which case the damper may be 
up to 8

1

2

 in. (216 mm) out of the 

barrier.

For more installation methods that are approved for ODFD-XXX and OFD-XXX series, go to www.greenheck.com. 
For access to inspect the damper and fusible link refer to the requirements of NFPA 90A.

Out of Wall Fire and Combination Fire Smoke Dampers

5

®

Содержание ODFD Series

Страница 1: ...injury or death Read the installation operating and maintenance instructions thoroughly before installing or servicing this equipment Table of Contents General Information 2 Installation Supplements...

Страница 2: ...l or floor opening annular space However caulking may be applied to the retaining angles 7 ACCESS Suitable access such that RRL s and actuators can be maintained etc must be provided for damper inspec...

Страница 3: ...fasteners must meet the requirements of the appropriate wall design See UL Fire Resistance Directory and or local codes Second set of studs are not required on openings 36 in x 36 in 914mm x 914mm or...

Страница 4: ...at the dampers may not be installed within the plane of the wall using this installation method Wooden Stud Construction Gypsum Wallboard Stud or Runner In wood stud construction gypsum wallboard must...

Страница 5: ...fire smoke damper 6 1 2 in Max 10 sheet metal screws 2 1 2 inches long spaced 6 in on center and maximum of 2 in from corners minimum of 2 screws per side Screw into rear portion of the studs so as to...

Страница 6: ...y a minimum of 1 in 25 mm See Figure 9 Retaining angles must be attached to the damper using one or more of the following methods of attachment Tack or spot welds 10 3 4 in 19 mm max sheet metal screw...

Страница 7: ...wide 1397 mm 2134 mm 22 ga 030 in 0 76 mm 31 in 54 in wide 787 mm 1372 mm 24 ga 0 024 0 6 mm 13 in 30 in wide 330 mm 762 mm 26 ga 0 018 in 0 46 mm 12 in wide and under 305 mm See Breakaway Connection...

Страница 8: ...ing S Alt Standing S Alt Standing S Standing S Bar Reinforced Angle Reinforced Figure 10 Drive Slip Joint Figure 11 Approved Breakaway Connections All breakaway connections described below may utilize...

Страница 9: ...t 4 Req d 48 in Duct 3 Req d 36 in Duct 3 Req d 24 in Duct 2 Req d 18 in Duct Smaller 1 Req d Clip Spacing Typical TDC TDF joint 6 in 6 in 9 in 7 in 7 in 5 in 5 in 5 in 5 in Figure 14 Manufactured Fla...

Страница 10: ...wo thermostats with fixed settings usually 165 F 74 C and 350 F 177 C The primary sensor the sensor with the lower temperature setting can be bypassed by an external contact closure allowing the dampe...

Страница 11: ...oting The following is a possible cause and correction list for common concerns with the dampers Symptom Possible Cause Corrective Action Damper does not fully open and or close Frame is racked causin...

Страница 12: ...s the right to change specifications without notice Product warranties can be found online at Greenheck com either on the specific product page or in the literature section of the website at Greenheck...

Отзывы: