Jet Fan
Installation
The component parts of the fan assembly, including
silencers, must be fully aligned before being bolted
together so that no stress is placed on the equipment.
After components are fully aligned, all bolts can be
tightened in an alternating pattern.
The examples shown below is installed using standard
mounting brackets. Before beginning installation,
reference the airflow direction as indicated by the
direction decal attached to the fan.
REMOVING FROM STORAGE
— As units are removed
from storage to be installed in their final location, they
should be protected and maintained in a similar fashion,
until the equipment goes into operation.
Prior to installing the unit and system components,
inspect the unit assembly to make sure it is in working
order.
1. Check all fasteners on the fan, propeller, motor base,
and accessories for tightness.
2. Rotate the fan propeller by hand and assure no parts
are rubbing.
Prop Cut Diameter for Std and High Temp
Outer
Tube
Inner
Tube
Minimum Tip
Clearance for
Standard Temp Fan
Minimum Tip
Clearance for
High Temp Fan
315
225
1.0
3.5
355
225
1.0
3.5
400
225
1.0
3.5
Propeller
Clearance
Blade
Interior of tube
Hub
Airflow
Wheel
Rotation
Decals
This is the label
for a model
GJ-AU.
C = ID
D = 2D
A
ID or 2D
B
Ø
Mounting Pattern
Unit Size
A
B
Ø
315-225
341
300
10
355-225
341
326
10
400-225
341
350
12
All dimensions are in millimeters.