Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting to assemble, 
install, operate or maintain the product described. Protect yourself and others by observing all safety 
information. Failure to comply with instructions could result in personal injury and/or property damage!

1

Downblast Centrifugal Roof Exhaust Fans

Model G
Direct Drive

Model G is a direct drive downblast 
centrifugal exhaust fan. These fans 
are specifically designed for roof 
mounted applications exhausting 
relatively clean air. Performance 
capabilities range up to 4,300 cfm 

(7,305 m

3

/hr)

 and up to 1 in. wg 

(249 Pa)

 of static pressure. The 

maximum continuous operating 
temperature is 180°F 

(82ºC)

G models are available in 27 sizes 
with nominal wheel diameter 
ranging from 8 to 24 inches 

(203 to 610  mm)

  (060 - 243 unit sizes).  Each  fan  shall 

bear a permanently affixed manufacturer’s engraved 
metal nameplate containing the model number and 
individual serial number. All fans are UL/cUL Listed 
Standard 705.

General Safety Information

Only qualified personnel should install this fan. 
Personnel should have a clear understanding of these 
instructions and should be aware of general safety 
precautions. Improper installation can result in electric 
shock, possible injury due to coming in contact with 
moving parts, as well as other potential hazards. Other 
considerations may be required if high winds or seismic 
activity are present. If more information is needed, 
contact a licensed professional engineer before moving 
forward.

1.  Follow all local electrical and safety codes, as 

well as the National Electrical Code (NEC) and the 
National Fire Protection Agency (NFPA), where 
applicable. Follow the Canadian Electrical Code 
(CEC) in Canada.

  2.  The rotation of the wheel is critical. It must be free 

to rotate without striking or rubbing any stationary 
objects.

  3.  Motor must be securely and adequately grounded.

  4.  Do not spin fan wheel faster than max cataloged 

fan RPM. Adjustments to fan speed significantly 
affects motor load. If the fan RPM is changed, the 
motor current should be checked to make sure it is 
not exceeding the motor nameplate amps.

  5.  Do not allow the power cable to kink or come in 

contact with oil, grease, hot surfaces or chemicals. 
Replace cord immediately if damaged.

  6.  Verify that the power source is compatible with the 

equipment.

  7.  Never open access doors to a duct while the fan is 

running.

Model GB
Belt Drive

GB model fans are belt drive 
downblast centrifugal exhaust fans. 
These fans are specifically designed 
for roof mounted applications 
exhausting relatively clean air. 
Performance capabilities range 
up to 44,700 cfm 

(75,950 m

3

/hr)  

and up to 2.5 in. wg 

(623 Pa)

 of 

static pressure. The maximum 
continuous operating temperature 
is 180°F 

(82ºC)

. GB models are 

available in twenty sizes with 
nominal wheel diameters ranging 

from 11 to 54 inches 

(279 to 1372 mm)

 (071-540 

unit sizes). Each fan shall bear a permanently affixed 
manufacturer’s nameplate containing the model 
number and individual serial number. All fans are 

 

UL/cUL Listed Standard 705.

DANGER

Always disconnect, lock and tag power source before 
installing or servicing. Failure to disconnect  power 
source can result in fire, shock or serious injury.

CAUTION

When servicing the fan, motor may be hot enough 
to cause pain or injury. Allow motor to cool before 
servicing.

CAUTION

Precaution should be taken in explosive atmospheres.

®

®

Document #471558

Model G and GB

Содержание G 060

Страница 1: ... the National Electrical Code NEC and the National Fire Protection Agency NFPA where applicable Follow the Canadian Electrical Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately grounded 4 Do not spin fan wheel faster than max cataloged fan RPM Adjustments to fan speed signi...

Страница 2: ...the bill of lading Handling G Direct Drive Lift unit on to the roof utilizing hooks under the lip of the shroud Evenly space the hooks around the shroud using a minimum of four lifting straps Use a spreader bar to ensure the straps do not come in contact with the unit see Figure 1 Figure 2 4 Drive Frame Lifting Points 2 Bearing Plate Lifting Points Hook With Safety Latch Supplied by others Figure ...

Страница 3: ...from leaking into the fan The fan should be elevated on an adequate number of wooden blocks so that it is above water and snow levels and has enough blocking to prevent it from settling into soft ground Locate parts far enough apart to permit air circulation sunlight and space for periodic inspection To minimize water accumulation place all fan parts on blocking supports so that rain water will ru...

Страница 4: ... 5 Secure fan to curb using a minimum of eight lag screws metal screws or the suitable fasteners Shims may be required depending upon curb installation and roofing material Note Severe duty applications may require additional fasteners 6 Verify power line wiring is de energized before connecting fan motor to power source 7 Connect power supply wiring to the motor as indicated on the motor nameplate...

Страница 5: ...200 200HP 30 762 18 457 20 521 138 63 GB 220 220HP 240 240HP 34 864 24 610 26 673 158 72 GB 260 40 1016 30 762 32 826 305 138 GB 300 300HP 40 1016 30 762 32 826 320 145 GB 330 46 1168 36 914 38 978 385 175 GB 360 360HP 46 1168 36 914 38 978 403 183 GB 420 52 1321 42 1067 44 1130 495 225 GB 480 52 1321 48 1219 50 1283 623 283 GB 500 64 1626 54 1372 56 1435 687 312 GB 540 64 1626 54 1372 56 1435 748...

Страница 6: ...10 GB 180 240 3 8 10 GB 260 540 1 2 13 Pre Starting Checks 1 Check all fasteners and set screws for tightness The wheel should rotate freely and be aligned as shown in Figure 7 below 2 Wheel position is preset and the unit is test run at the factory Movement may occur during shipment and realignment may be necessary 3 Only G unit Centering height alignment can be accomplished by loosening the set ...

Страница 7: ...Inspection Inspection of the fan should be conducted at the first 30 minute and 24 hour intervals of satisfactory operation 30 Minute Interval Inspect bolts setscrews and motor mounting bolts Adjust and tighten as necessary 24 Hour Interval Check all internal components On GB unit only inspect belt alignment and tension Adjust and tighten as necessary Maintenance G GB Installation and maintenance a...

Страница 8: ...S A Inc Chevron SRI Grease 2 Mobil Oil Corporation Mobilith Mobil 532 Texaco Inc Premium BRB 2 Texaco Multifak 2 Amoco Oil Co Rykon Premium 2 Exxon Unirex N2 Shell B Shell Alvania 2 Table 2 Suggested Fan Bearing Greasing Intervals Interval months Type of Service 1 to 3 Heavy duty in dirty dusty locations high ambient temperatures moisture laden atmosphere vibration 3 to 6 12 to 24 hours per day he...

Страница 9: ...ypass dampers Check filters and access doors Fan does not operate Electrical supply Check fuses circuit breakers Check for switches off Check for correct supply voltage Drive Check for broken belts Tighten loose pulleys Motor Assure motor is correct horsepower and not tripping overload protector Motor overloads or overheats Lubrication Check for excessive or insufficient grease in the bearing Mechan...

Страница 10: ..._____ _________________________________________________ Date ___________________Time _____________ AM PM Notes ___________________________________________ _________________________________________________ _________________________________________________ _________________________________________________ Date ___________________Time _____________ AM PM Notes ________________________________________...

Страница 11: ...y Drive Frame Assembly Conduit Chase Shock Mounts Shroud Vertical Support Bearings G Direct Drive Centrifugal Roof Exhaust Fan GB Belt Drive Centrifugal Roof Exhaust Fan Parts List NOTE Each fan bears a manufacturer s nameplate with model number and serial number embossed This information will assist the local representative and the factory in providing service and replacement parts Before taking ...

Страница 12: ...ry under Warranties Greenheck Centrifugal Roof Downblast Exhaust Fan catalog provides additional information describing the equipment fan performance available accessories and specification data Phone 715 359 6171 Fax 715 355 2399 Parts 800 355 5354 E mail gfcinfo greenheck com Website www greenheck com Our Commitment AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial a...

Отзывы: