Installation, Operation and Maintenance Instructions

Part Number 461666

Safety Warning:

 

Improper installation, adjustment, alteration, service 
or maintenance can cause property damage, injury or 
death. Read the installation, operating, and maintenance 
instructions thoroughly before installing or servicing this 
equipment.

This manual is the property of the owner, and is required for future maintenance. Please leave it with the owner when 
the job is complete.

Warranty

Greenheck warrants this equipment to be free from 
defects in material and workmanship for a period of one 
year from the purchase date. Any units or parts which 
prove to be defective during the warranty period will 
be repaired or replaced at our option. Greenheck shall 
not be liable for damages resulting from misapplication 
or misuse of its products. Greenheck will not be 
responsible for any installation or removal costs. 
Greenheck will not be responsible for any service work 
or backcharges without prior written authorization. 

Due to continuing research, Greenheck reserves the right to change specifications without notice.

“UL CLASSIFIED (see complete marking on 

product)”

“UL CLASSIFIED to Canadian safety standards 

(see complete marking on product)”

 

UL Standard 555 & 555S (Classification R13317)

FSD-3XXV Series Dampers are intended for installation 

in accordance with combination fire smoke damper 

requirements established by:

National Fire Protection Association  

 

NFPA Standards 80, 90A, 92A, 92B, 101, & 105

BOCA 

National Building Codes

ICBO 

Uniform Building Codes

IBC

 International Building Codes

SBCCI 

Standard Building Codes

New York City 

(MEA listing #260-91-M)

California State Fire Marshal 

 

Listing #3225-0981:103 and 3230-0981:104

Receiving and Handling

Upon receiving dampers, check for both obvious 
and hidden damage. If damage is found, record all 
necessary information on the bill of lading and file 
a claim with the final carrier. Check to be sure that 
all parts of the shipment, including accessories, are 
accounted for.
Dampers must be kept dry and clean. Indoor storage 
and protection from dirt, dust and the weather is highly 
recommended. Do not store at temperatures in excess 
of 100°F (38°C).

Typical 
Actuator

RRL Control 
Device Standard

FSD-3XXV Series 

1 1/2 Hour

Combination Fire Smoke Dampers 

( with factory installed sleeve and actuator) 

Vertical Blade

Installation Supplements

Refer to the appropriate Greenheck installation 
supplements for special requirements:
 

• Metal Stud in Shaftwall 

 

• Metal Stud in Drywall 

 

• Wood Stud in Shaftwall 

 

• Smoke Detector 

 

• No Flow Smoke Detector 

 

• Tunnel Corridor 

 

• Single Side Retaining Angle 

 

• Grille Installation 

 

• Field Installed Sleeve 

 

• Quick Connect Breakaway Connections 

 

• Sealant Supplement 

 

• Fire Resistant Ventilated Duct Assembly 

 

• Drive Slip Breakaway Connection 

 

• Concrete Floor with Steel Deck 

 

• Sleeve Extension 

 

• Open or Close Indicator 

 

• Resettable Link

Содержание FSD-3XXV Series

Страница 1: ...dance with combination fire smoke damper requirements established by National Fire Protection Association NFPA Standards 80 90A 92A 92B 101 105 BOCA National Building Codes ICBO Uniform Building Codes IBC International Building Codes SBCCI Standard Building Codes New York City MEA listing 260 91 M California State Fire Marshal Listing 3225 0981 103 and 3230 0981 104 Receiving and Handling Upon rec...

Страница 2: ...e installed into duct or opening square and free of twist or other misalignment Damper must not be squeezed or stretched into duct or opening Out of square racked twisted or misaligned installations can cause excessive leakage and or torque requirements to exceed damper actuator design 6 Damper and actuator must be kept clean and protected from dirt dust and other foreign materials prior to and af...

Страница 3: ...l floor openings are Galvanized steel fire dampers and sleeves 1 8 in 3mm per foot of damper width and height with a minimum clearance of 1 4 in 6mm maximum of 1 1 2 in 38mm Recommended clearances for width and or height dimensions of 1 36 in 914mm or less 1 2 in 13mm clearance These are total clearances ignoring fastener heads and do not need to be equally spaced around the damper 2 SLEEVE LENGTH...

Страница 4: ... be attached to the damper using one or more of the following methods of attachment refer to label on outside of sleeve for No Screw area Tack or spot welds 10 3 4 in max 19mm sheet metal screws 1 4 in 6mm bolts and nuts 3 16 in 5mm steel pop rivets A minimum of two connections per side top and bottom 12 in 305mm O C maximum for openings of 48 in W x 32 in H 1219mm x 812mm and less and 6 in 152mm ...

Страница 5: ...he TOR thermostats and indicator switches If either the TOR or the RRL is ordered with a pneumatic actuator an EP switch is required with an appropriate electric power circuit to allow the electric thermostat to control the pneumatic actuator PRV The PRV pneumatic relief valve option is heat responsive device used with pneumatic actuators This can be used in place of EP switch where a RRL is used ...

Страница 6: ...each side and on the bottom located in the center of the slip pocket and penetrating both sides of the slip pocket Transverse joints illustrated can be applied as top and bottom joints with Drive Slip side joints in duct heights up to 20 inches 508mm see Fig 10 Round and Oval Duct Breakaway Connections Round or flat oval ducts connected to Type R or O damper collars shall be attached with 10 19mm ...

Страница 7: ...ls do not use oil based lubricants or any other lubricants that attract contaminants such as dust Dampers and their actuator s must be maintained cycled and tested a minimum in accordance with The latest editions of NFPA 80 90A 92A 92B 101 105 UL864 AMCA 503 03 and local codes Actuator manufacturer recommendations Damper Troubleshooting The following is a possible cause and correction list for com...