Combination Fire Smoke Dampers meeting the following specifica-
tions shall be furnished and installed where shown on plans and/or 
as described in schedules. Dampers shall meet the requirements of 

NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall be teste

d

, rated 

and labeled in accordance with the latest edition of UL Standards 
555 and 555S.  Dampers shall have a UL555 fire rating of 1½ hours 
and be of low leakage design qualified to UL 555S Leakage Class II.

Each damper /actuator combination shall have a UL555S elevated 
temperature rating of 250° F (121°C) minimum and shall be opera-
tional and dynamic rated to operate at maximum design air flow at 
its installed location. Each damper shall be supplied with an appro-
priate actuator installed by the damper manufacturer at the time of 
damper fabrication. Damper actuator shall be (specifier select one 
of the following) electric type for 120 (24 or 230) volt operation 

or

 

pneumatic type for 25 psi minimum (30 psi maximum) operation.

Damper blades shall be of the double skin airfoil type and shall 
have an equivalent thickness of 14 ga. (2mm) . Damper frame shall 

be galvanized steel formed into a structural hat channel shape with 
reinforced corners. Bearings shall be sintered bronze sleeve type 
rotating in extruded holes in the damper frame. Blade edge seals 
shall be silicone rubber designed to inflate and provide a tighter seal 
against leakage as pressure on either side of the damper increases. 
Jamb seals shall be stainless steel compression type. Blades shall 

be completely symmetrical relative to their axle pivot point, present

-

ing identical resistance to airflow in either direction or pressure on 
either side of the damper.

Damper must be rated for mounting vertically (with blades running 
horizontal) or horizontally and be UL 555S rated for leakage and 
airflow in either direction through the damper. Each damper shall be 

supplied with a 165°F (74°C) RRL. Testing and ratings to be in ac

-

cordance with AMCA standard 500-D.

The basis of design is Greenheck Model FSD-312.

damper sizing Information

Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size.  The 

following figures show maximum damper section size and assembly configurations for multi-section dampers.

specifications

Transitioned damper 

dimensions

When a fire/smoke damper is being used in conjunction with round or oval ductwork, the

 

FSD-312 can be supplied in a factory sleeve with round or oval transitions on both ends of 

the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show over-

all damper size.

These dimensions are furnished

 

approximately 

1

/

4

 in. (6mm) undersize, 

except round and oval  dimensions  

which are approximately 

1

/

8

 in.(3mm) 

undersize. 

T

= (2)(Sleeve Thickness)

D*  +  2 in. (51mm) +T  s 

D* 

TYPE  R 

 

16 in. (406mm) 

Min. 

8

 in.

D*  +  2 in. (51mm)+T  s 

TYPE  O 

H* 

W* 

  

+  2 in. (51mm)+T s 

H*  +  2 in. (51mm)+T s 

W* 

H* 

TYPE  C 

  

H*  +  2 in. (51mm)+T s 

 

(54mm)

16 in. (406mm) 

Min. 

8

 in. 

(54mm)

16 in. (406mm) 

Min. 

W* +  2 in. (51mm)+T s 

(54mm)

8

 in.

Copyright © 2006 Greenheck Fan Corporation

FSD-312 Rev 3 June 2006

Содержание FSD-312

Страница 1: ...l Features RRL OCI Open closed indication switches 165 F 74 C 212 F 100 C 250 F 121 C 350 F 177 C RRL s available TOR remote override closure allows damper to perform smoke management functions during...

Страница 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstr...

Страница 3: ...ure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 03 500 0 01 500 0 01 500 0 01 500 0 02 1000 0 1...

Страница 4: ...Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 01 500 0 01 500 0 01 500 0 01 500 0 01 1000 0 06 1000 0 02 1000 0 02 1000 0 02 1000 0 04 1500 0 13 1500 0 06...

Страница 5: ...Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 04 500 0 03 500 0 03 500 0 03 500 0 03 1000 0 18 1...

Страница 6: ...ft hand drive available upon request LH RH A Sleeve Length Varies 6 33 4 11 2 max B S T The standard location of a damper mounted in a factory sleeve A dimension is shown below The damper can be posit...

Страница 7: ...to inflate and provide a tighter seal against leakage as pressure on either side of the damper increases Jamb seals shall be stainless steel compression type Blades shall be completely symmetrical rel...

Отзывы: