APPLICATION

Model FSD-312 is a high performance combination fire smoke 

damper with class II leakage. High strength airfoil blades ensure the 

lowest resistance to airflow in HVAC systems with velocities to 3000 

fpm (15.2 m/s) and pressures to 4 in. wg (1 kPa) Model FSD-312 may 

be installed vertically (with blades running horizontal) or horizontally 

and is rated for airflow and leakage in either direction.

RATINgs

UL 555 Fire Resistance Rating:

 

 

Fire Rating:

 

1½ hours 

 

Dynamic Closure Rating:

 Actual ratings are size dependent 

 

Max. Velocity:

 

up to 3000 fpm (15.2 m/s) 

 

Max. Pressure:

 

4 in. wg (1 kPa)

UL555S Leakage Rating:

 

 

Leakage Class:

 

II 

 

Operational Rating:

 

Actual ratings are size dependent 

 

Max. Velocity:

 

up to 3000 fpm (15.2m/s) 

 

Max. Pressure:

 

4 in. wg (1 kPa) 

 

Maximum Temperature:

  350°F (177°C)- depending upon the 

 

 

actuator

sTANdARd CONsTRuCTION

 

Frame:

  

5 in. x 1 in. (127mm x 25 mm) 

 

 

galvanized steel hat channel with 

 

 

reinforced corners. A low profile 

 

 

head and sill are used on sizes less 

 

 

than 17 in. (432mm) 

 

Blades:

  

Double skin airfoil shape of 

 

 

galvanized steel with full length 

 

 

structural reinforcement.  14 ga. 

 

 

(2 mm) equivalent thickness. 

 

seals:

 

Extruded silicone rubber blade seals.  

 

 

Flexible stainless steel jamb seals. 

 

Linkage:

 

Concealed in jamb. 

 

Closure device:

 

RRL 165°F (74°C) 

 

Axles:

 

1⁄2 in. (13mm) dia. plated steel. 

 

Bearings:

 

Bronze sleeve type.

sIze LImITATIONs:

 

minimum size:

 

8 in. W x 6 in. H 

 

 

(203 mm W x 152mm H) 

 

maximum size:

 

 

Single Section: 

32 in. W x 50 in. H 

 

 

(813mm W  x 1270mm H) 

 

Multiple Section: 

96 in. W x 50 in. H 

 

 

(2435mm W x 1270mm H) 

 

Vertical Only: 

128 in.  W x 100 in. H 

 

 

(3251mm  W x 2540mm H)

OPTIONAL FeATuRes:

• RRL/OCI (Open closed indication switches)

 

• 165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL’s

 

  available 

• TOR (remote override closure allows damper to perform smoke

 

  management functions during a fire emergency.) 

• Electric or pneumatic actuators to accomplish smoke

 

  management and system functions. 

• POC retaining angles

 

• Smoke detectors

 

• Momentary Switch

 

• Transitions (R, C, O)

 

• PRV (pneumatic relief valve)

 

• Security Bars

 

• Sealed transitions and sleeves

model Fsd-312 

Combination Fire smoke dampers

Steel Airfoil Blades

UL 555S Leakage Class II

UL555 1

1

2

 Hour Fire Resistance Rating

*W&H dimensions furnished approximately 1/4 in. ( 6 mm) undersize.

(Add sleeve thickness for overall sleeved damper dimension)

Right hand drive is shown. Left hand drive is available upon request.

H*

W*

LH

RH

Model FSD-312 meets the requirements for fire 

dampers, smoke dampers and combination fire 

smoke dampers established by:

National Fire Protection Association 

 

NFPA Standards 80, 90A, 92A, 92B, 101 & 105

 

IBC  International Building Codes 
ICBO  uniform Building Codes 
CsFm California state Fire marshal 
 

Fire Damper Listing (#3225-0981:103) 

  Leakage (Smoke) Damper Listing (#3230-0981:104) 

New York City 

(MEA listing #260-91-M)

“uL CLAssIFIed (see complete marking on prod-

uct)” 

“uL CLAssIFIed to Canadian safety standards 

(see complete marking on product)” 

Standard 555 & 555S (Listing #R13317)

R

Greenheck Fan Corporation certifies that the 

model FSD-312 shown herein is licensed to 

bear the AMCA Seal. The ratings shown are 

based on tests and procedures performed 

in accordance with AMCA Publication 511 

and comply with the requirements of the 

AMCA Certified Ratings Programs. The 

AMCA Certified Ratings Seal applies to air 

performance ratings only.

Installation instructions available at www.greenheck.com

Содержание FSD-312

Страница 1: ...l Features RRL OCI Open closed indication switches 165 F 74 C 212 F 100 C 250 F 121 C 350 F 177 C RRL s available TOR remote override closure allows damper to perform smoke management functions during...

Страница 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstr...

Страница 3: ...ure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 03 500 0 01 500 0 01 500 0 01 500 0 02 1000 0 1...

Страница 4: ...Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 01 500 0 01 500 0 01 500 0 01 500 0 01 1000 0 06 1000 0 02 1000 0 02 1000 0 02 1000 0 04 1500 0 13 1500 0 06...

Страница 5: ...Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg Velocity fpm Pressure Drop in wg 500 0 04 500 0 03 500 0 03 500 0 03 500 0 03 1000 0 18 1...

Страница 6: ...ft hand drive available upon request LH RH A Sleeve Length Varies 6 33 4 11 2 max B S T The standard location of a damper mounted in a factory sleeve A dimension is shown below The damper can be posit...

Страница 7: ...to inflate and provide a tighter seal against leakage as pressure on either side of the damper increases Jamb seals shall be stainless steel compression type Blades shall be completely symmetrical rel...

Отзывы: