Model FDR-510 meets the requirements for fire dampers 

established by:

National Fire Protection Association 

(NFPA Standards 80, 90A & 101)

Underwriters Laboratories Standard 555 
 

(Listing #R-13317)

IBC  International Building Codes

Model FDR-510

 

Static Rated

 

Round Fire Dampers

1

1

/

2

 Hour Fire Resistance Rating

Copyright ©2008 Greenheck Fan Corporation

FDR-510 Rev. 6

 

Aug  2008

These dimensions are furnished approximately 1/8 in. (3mm) 

    smaller  than nominal. 

Features:

• Stainless steel closure springs
•  Fusible links - 165ºF (74ºC) standard;  212ºF (100ºC) and 286ºF 

(141ºC) available

• Can be mounted horizontally or vertically
•  Only one retainer plate required (one retainer plate supplied 

with damper)

• Additional retainer plate available
• 14 ga. (2mm) or 16 ga. (1.5mm) frame/sleeve

Application and Design

Model FDR-510 is a round fire damper for use in walls or 
partitions with less than 3 hour fire resistance rating. It is 

qualified to be mounted vertically and horizontally. This 

model carries a 1 1/2 hour UL fire damper label. UL555 
classifies static rated fire dampers for use in HVAC systems 
that are automatically shut down in the event of fire.

Ratings

 

 

Temperature: 

165º F  (74ºC)

Standard Construction

 

Frame/Sleeve:  20 ga. (1mm) galvanized steel

 

 

Blade:  20 ga. (1mm) galvanized steel

 

 

Closure Device:  165ºF (82ºC) Fusible Link

 

 

Axle: 

1

/

2

 in. (6mm) dia. plated steel. 

 

Bearing:  Stainless Steel sleeve type

Size Limitations

 

Minimum size:  4 in. (102mm) diameter

 

 

Maximum size:  24 in. (610mm) diameter

O 2.00 MIN.

FASTENERS

WALL/FLOOR

1.00 TYP.

= Nominal size + 7/8 Min.

OPENING

CLAMPING SCREW

RETAINING

PLATE ASSEMBLY

NUT

SCREW

CLAMPING

WALL THICKNESS 

SLEEVE LENGTH

Up to 6.5 

 

13.625

Up to 8.5 

 

15.625

Up to 10.5 

 

17.625

Over 10.5 

 

Consult Greenheck

2 in.

TW

AIRFLOW

SLEEVE LENGTH

2 in.

6 in. max.

6 in. max.

(OPTIONAL)

RETAINER PLATE

DUCT CONNECTION

AREA

CLEARANCE FOR

EXPANSION

RETAINER PLATE

BLADE LATCH

ACCESS DOOR TO BE ON

SAME SIDE AS BLADE LATCH

DUCT CONNECTION

AREA

DO NOT PLACE RETAINER

PLATE IN THIS GROOVE

Installation instructions available at www.greenheck.com.