Energy Core Ventilator

7

®

Roof Curb Mounting

Rooftop units require curbs to be mounted first. The 
duct connections must be located so they will be clear 
of structural members of the building.

  1.  Factory Supplied Roof Curbs: 

Roof curbs are 

Model GKD. The GKD ships in a knockdown kit 
(includes duct adapter) and requires field assembly 
(by others). Assembly instructions are included.

  2.  Install Curb: 

Locate curb over roof opening and 

fasten in place. (Refer to Recommended Roof 
Openings). Check that the diagonal dimensions 
are within ±1/8 inch of each other and adjust as 
necessary. For proper unit operation, it is important 
that the installation be level. Shim as required to 
level. 

  3.  Install Ductwork: 

Installation of all ducts should 

be done in accordance with SMACNA and AMCA 
guidelines. Duct adapter provided to support ducts 
prior to setting the unit. 

  4.  Set the Unit: 

Lift unit to a point directly above the 

curb and duct openings. Guide unit while lowering 
to align with duct openings. Roof curbs fit inside 
the unit base. Make sure the unit is properly seated 
on the curb and is level.

  5.  Fasten the Unit: 

Fasten the unit to the curb/

equipment support(s) using appropriate methods. 
The installer is responsible for determining 
appropriate support and fastening methods to 
ensure compliance with all applicable codes.

Unit Size

A

B

C

D

E

ECV-10

1.9

5.3

4.3

0.8

0.4

ECV-20

1.9

6.8

5.8

1.6

0.4

ECV-30

1.9

6.8

5.8

1.6

0.4

ECV-40

1.9

6.8

5.8

1.6

0.4

All dimensions are in inches.

Roof Curb

Side of Unit

Base

1-inch Insulation

E

D

C

A

B

Curb Cap Details for Factory-Supplied Roof Curbs

Unit 

Size

A

B

C

D

Curb 

Weight 

(lbs.)

ECV-10 52.3 26.4 16.5 x 11.5

8.5 x 11.6

60

ECV-20 55.8 39.8

28 x 13.5

25.2 x 15.6

79

ECV-30 55.8 57.7 47.5 x 13.5

42.7 x 15.6

95

ECV-40 55.8 76.8 66.7 x 13.5

54 x 15.6

110

All dimensions are in inches. Weight is for 14-inch high 

model GKD curbs.

Curb Outside Dimensions and Weights

A

B

C

D

Содержание ECV Series

Страница 1: ...plicable Follow the Canadian Electrical Code CEC in Canada 2 All moving parts must be free to rotate without striking or rubbing any stationary objects 3 Unit must be securely and adequately grounded...

Страница 2: ...contactor in the air handler closes to start the unit Summer Operation Outdoor air is preconditioned temperature and moisture levels are decreased by the transfer of energy from the cooler drier retu...

Страница 3: ...nt condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose t...

Страница 4: ...AIR INTAKE OUTDOOR AIR INTAKE A B C EXHAUST AIR DISCHARGE SUPPLY AIR DISCHARGE NON ELECTRICAL SIDE D G E F Top and Bottom Connections Top and End Connections OUTDOOR AIR INLET A B C EXHAUST AIR DISCH...

Страница 5: ...Discharge End Recommended Minimum Recommended Minimum Weatherhood Yes Weatherhood No Weatherhood Yes Weatherhood No ECV 10 30 20 30 No Access Required 33 No Access Required 24 No Access Required ECV...

Страница 6: ...r replacement and maintenance Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary Lifting WARNING All factory provided li...

Страница 7: ...et the Unit Lift unit to a point directly above the curb and duct openings Guide unit while lowering to align with duct openings Roof curbs fit inside the unit base Make sure the unit is properly seat...

Страница 8: ...52 x 16 6 Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute FPM at minimum airflow and up to 1600 fpm at maximum airflow Recommende...

Страница 9: ...em Voltage Supply See voltage use range on the rating plate Measure and record each supply leg voltage at all line disconnect switches Readings must fall within the allowable range on the rating plate...

Страница 10: ...to switch Dirty filter light Economizer light Frost control light On Off Auto Switch Indictor Light Wiring Typical Control Center Components 1 Main Disconnect nonfusible lockable 2 Motor Starter Exhau...

Страница 11: ...VG reference unit wiring diagram ST2 M1 WHITE T1 T3 SUPPLY FAN MOTOR 15 16 0 10VDC BLACK POT BLACK 2CBL M1 RED RED CLOSED 115 120V OPEN 208 230 277V M2 EXHAUST FAN MOTOR 17 18 0 10VDC POT BLACK RED RE...

Страница 12: ...ature and enable the preheater if required If the temperature falls below the set point the electric preheater will turn on Access to the electric preheat is through the outdoor air filter access door...

Страница 13: ...Unit Serial Number ________________________________ e g 04C99999 or 10111000 Start Up Date ________________________________ Start Up Personnel Name___________________________ Start Up Company ________...

Страница 14: ...thermostat 36 F Differential 2 F Timer Refer to page 17 Economizer Application Operation section Yes No Economizer temperature Set point 65 F Offset 20 F Differential 2 F Yes No Economizer enthalpy S...

Страница 15: ...AUTION When operating conditions of the fan are to be changed speed pressure temperature etc consult Greenheck to determine if the unit can operate safely at the new conditions Direction of Fan Wheel...

Страница 16: ...CHANGE STORED displays 9 Press enter to return the current menu parameter 10 Press escape to return to the current menu parameter When values are displayed pressing and holding the or button causes t...

Страница 17: ...PPM CO2 Variable Frequency Drive The ECV 20 and ECV 30 are wired to the Variable Frequency Drive VFD Refer to the Variable Frequency Drive section for control sequence and programming Timer Scale Time...

Страница 18: ...ctory set points refer to Yaskawa VFD instruction manual which can be found online at www drives com MAMBMC RP H1 SC HC S7 S6 S5 S4 S3 S2 S1 MP AC AM AC V A2 A1 PC P2 P1 IG S S R R V1000 MAMBMC AC AM...

Страница 19: ...er rectangular panel This will allow access to the supply blower that is located on the control side of the housing Replace panel after service reinstall core support that was removed then reinstall c...

Страница 20: ...power to the unit Remove access panel Removing the energy recovery core Once the energy core access doors are removed the core can be pulled from the housing To replace the core reverse the procedure...

Страница 21: ...consult the factory Clearing Alarms Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the...

Страница 22: ...w prior to contacting the factory please determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SM...

Страница 23: ...power too low See specifications and catalog for fan curves to determine if horsepower is sufficient Shorted windings in motor Replace motor Low airflow cfm Unit damper not fully open Adjust damper li...

Страница 24: ...Resources Library Literature Greenheck catalog Energy Core Ventilators Model MiniCore and ECV provides additional information describing the equipment fan performance available accessories and specif...

Отзывы: