Energy Core Ventilator

3

®

Receiving

This product may have been subject to road salt 
during transit. If so, immediately wash off all visible 
white reside from all exterior surfaces. Upon receiving 
the product, check to ensure all items are accounted 
for by referencing the delivery receipt or packing list. 
Inspect each crate or carton for shipping damage before 
accepting delivery. Alert the carrier if any damage is 
detected, 

do not refuse shipment

. The customer shall 

make notation of damage (or shortage of items) on the 
delivery receipt and all copies of the bill of lading should 
be countersigned by the delivering carrier. If damaged, 
immediately contact your manufacturer’s representative. 
Any physical damage to the unit after acceptance is not 
the responsibility of the manufacturer.

Handling

Units are to be rigged and moved by the lifting brackets 
provided or by the skid when a forklift is used. Location 
of brackets varies by model and size. Handle in such 
a manner as to keep from scratching or chipping the 
coating. Damaged finish may reduce ability of unit to 
resist corrosion.

Unpacking

Verify that all required parts and the correct quantity of 
each item have been received. Inspect interior of unit 
cabinet for any shipped loose items. If any items are 
missing, report shortages to your local representative to 
arrange for obtaining missing parts. Sometimes it is not 
possible that all items for the unit be shipped together 
due to availability of transportation and truck space. 
Confirmation of shipment(s) must be limited to only 
items on the bill of lading.

Storage

Units are protected against damage during shipment. If 
the unit cannot be installed and operated immediately, 
precautions need to be taken to prevent deterioration of 
the unit during storage. The user assumes responsibility 
of the unit and accessories while in storage. The 
manufacturer will not be responsible for damage during 
storage. These suggestions are provided solely as a 
convenience to the user.
The ideal environment for the storage of units and 
accessories is indoors, above grade, in a low humidity 
atmosphere which is sealed to prevent the entry of 
blowing dust, rain, or snow. Units designed for outdoor 
applications may be stored outdoors. All accessories 
must be stored indoors in a clean, dry atmosphere. 

Indoor

Maintain temperatures evenly to prevent condensation. 
Remove any accumulations of dirt, water, ice, or snow 
and wipe dry before moving to indoor storage. To 
avoid condensation, allow cold parts to reach room 
temperature. Leave coverings loose to permit air 
circulation and to allow for periodic inspection.

The unit should be stored at least 3½ in. (89 mm) off 
the floor. Clearance should be provided to permit air 
circulation and space for inspection.

Outdoor

The unit should be placed on a level surface to prevent 
water from leaking into the unit. The unit should be 
elevated so that it is above water and snow levels. 
Ensure sufficient support to prevent unit from settling 
into soft ground. Locate parts far enough apart to 
permit air circulation, sunlight, and space for periodic 
inspection. To minimize water accumulation, place all 
unit parts on blocking supports so that rain water will 
run off.
Do not cover parts with plastic film or tarps as these 
cause condensation of moisture from the air passing 
through heating and cooling cycles.

Inspection and Maintenance

While in storage, inspect units once per month. Keep a 
record of inspection and maintenance performed.
If moisture or dirt accumulations are found on parts, 
the source should be located and eliminated. At each 
inspection, rotate the fan wheel by hand ten to fifteen 
revolutions to distribute lubricant on motor. If paint 
deterioration begins, consideration should be given to 
touch-up or repainting. Units with special coatings may 
require special techniques for touch-up or repair.
Machined parts coated with rust preventive should be 
restored to good condition promptly if signs of rust 
occur. Immediately remove the original rust preventive 
coating with petroleum solvent and clean with lint-free 
cloths. Polish any remaining rust from surface with 
crocus cloth or fine emery paper and oil. Do not destroy 
the continuity of the surfaces. Wipe thoroughly clean 
with Tectyl

®

 506 (Ashland Inc.) or the equivalent. For 

hard to reach internal surfaces or for occasional use, 
consider using Tectyl

®

 511M Rust Preventive, WD-40

® 

or the equivalent.

Removing from Storage

As units are removed from storage to be installed 
in their final location, they should be protected and 
maintained in a similar fashion until the equipment goes 
into operation.
Prior to installing the unit and system components, 
inspect the unit assembly to make sure it is in working 
order.
1.  Check all fasteners, set screws on the fan, wheel, 

bearings, drive, motor base, and accessories for 
tightness.

2.  Rotate the fan wheel(s) by hand and assure no parts 

are rubbing.

Содержание ECV Series

Страница 1: ...plicable Follow the Canadian Electrical Code CEC in Canada 2 All moving parts must be free to rotate without striking or rubbing any stationary objects 3 Unit must be securely and adequately grounded...

Страница 2: ...contactor in the air handler closes to start the unit Summer Operation Outdoor air is preconditioned temperature and moisture levels are decreased by the transfer of energy from the cooler drier retu...

Страница 3: ...nt condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose t...

Страница 4: ...AIR INTAKE OUTDOOR AIR INTAKE A B C EXHAUST AIR DISCHARGE SUPPLY AIR DISCHARGE NON ELECTRICAL SIDE D G E F Top and Bottom Connections Top and End Connections OUTDOOR AIR INLET A B C EXHAUST AIR DISCH...

Страница 5: ...Discharge End Recommended Minimum Recommended Minimum Weatherhood Yes Weatherhood No Weatherhood Yes Weatherhood No ECV 10 30 20 30 No Access Required 33 No Access Required 24 No Access Required ECV...

Страница 6: ...r replacement and maintenance Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary Lifting WARNING All factory provided li...

Страница 7: ...et the Unit Lift unit to a point directly above the curb and duct openings Guide unit while lowering to align with duct openings Roof curbs fit inside the unit base Make sure the unit is properly seat...

Страница 8: ...52 x 16 6 Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute FPM at minimum airflow and up to 1600 fpm at maximum airflow Recommende...

Страница 9: ...em Voltage Supply See voltage use range on the rating plate Measure and record each supply leg voltage at all line disconnect switches Readings must fall within the allowable range on the rating plate...

Страница 10: ...to switch Dirty filter light Economizer light Frost control light On Off Auto Switch Indictor Light Wiring Typical Control Center Components 1 Main Disconnect nonfusible lockable 2 Motor Starter Exhau...

Страница 11: ...VG reference unit wiring diagram ST2 M1 WHITE T1 T3 SUPPLY FAN MOTOR 15 16 0 10VDC BLACK POT BLACK 2CBL M1 RED RED CLOSED 115 120V OPEN 208 230 277V M2 EXHAUST FAN MOTOR 17 18 0 10VDC POT BLACK RED RE...

Страница 12: ...ature and enable the preheater if required If the temperature falls below the set point the electric preheater will turn on Access to the electric preheat is through the outdoor air filter access door...

Страница 13: ...Unit Serial Number ________________________________ e g 04C99999 or 10111000 Start Up Date ________________________________ Start Up Personnel Name___________________________ Start Up Company ________...

Страница 14: ...thermostat 36 F Differential 2 F Timer Refer to page 17 Economizer Application Operation section Yes No Economizer temperature Set point 65 F Offset 20 F Differential 2 F Yes No Economizer enthalpy S...

Страница 15: ...AUTION When operating conditions of the fan are to be changed speed pressure temperature etc consult Greenheck to determine if the unit can operate safely at the new conditions Direction of Fan Wheel...

Страница 16: ...CHANGE STORED displays 9 Press enter to return the current menu parameter 10 Press escape to return to the current menu parameter When values are displayed pressing and holding the or button causes t...

Страница 17: ...PPM CO2 Variable Frequency Drive The ECV 20 and ECV 30 are wired to the Variable Frequency Drive VFD Refer to the Variable Frequency Drive section for control sequence and programming Timer Scale Time...

Страница 18: ...ctory set points refer to Yaskawa VFD instruction manual which can be found online at www drives com MAMBMC RP H1 SC HC S7 S6 S5 S4 S3 S2 S1 MP AC AM AC V A2 A1 PC P2 P1 IG S S R R V1000 MAMBMC AC AM...

Страница 19: ...er rectangular panel This will allow access to the supply blower that is located on the control side of the housing Replace panel after service reinstall core support that was removed then reinstall c...

Страница 20: ...power to the unit Remove access panel Removing the energy recovery core Once the energy core access doors are removed the core can be pulled from the housing To replace the core reverse the procedure...

Страница 21: ...consult the factory Clearing Alarms Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the...

Страница 22: ...w prior to contacting the factory please determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SM...

Страница 23: ...power too low See specifications and catalog for fan curves to determine if horsepower is sufficient Shorted windings in motor Replace motor Low airflow cfm Unit damper not fully open Adjust damper li...

Страница 24: ...Resources Library Literature Greenheck catalog Energy Core Ventilators Model MiniCore and ECV provides additional information describing the equipment fan performance available accessories and specif...