Energy Core Ventilator
14
®
Optional Accessories Checklist
Refer to the respective sections in this Installation, Operation and Maintenance Manual for detailed information.
Refer to wiring diagram in unit control center to determine what electrical accessories were provided.
Provided with Unit?
Frost Control Application / Operation section:
Setting
Factory Default
Yes
No
Frost Control thermostat
36ºF
Differential
2ºF
Timer
Refer to page 17
Economizer Application / Operation section:
Yes
No
Economizer (temperature)
Set point
65ºF
Offset
20ºF
Differential
2ºF
Yes
No
Economizer (enthalpy)
Set point
D
Optional Accessories section:
Operational
Yes
No
OA Dirty Filter Sensor
Yes No N/A
Yes
No
EA Dirty Filter Sensor
Yes No N/A
Yes
No
CO
2
Sensor
Yes No N/A
Yes
No
Remote Control Panel
Yes No N/A
Variable Frequency Drives section:
Operational
Yes
No
Blower VFDs
Yes No N/A
Damper section:
Operational
Yes
No
Outdoor Air Damper
Yes No N/A
Yes
No
Exhaust Air Damper
Yes No N/A