background image

Energy Core Ventilator

13

®

Start-Up

Pre Start-Up Checklist 

 

check as items are 

completed.

o

  Disconnect and lock-out all power switches

o

  Remove any foreign objects that are located in the 

energy recovery unit.

o

  Check all fasteners, set-screws, and locking collars 

on the fans, motor bases and accessories for 
tightness.

o

  Rotate the fan wheels by hand to ensure no parts are 

rubbing. If rubbing occurs, refer to Start-Up section 
for more information.

o

  Confirm the EC motor voltage is correct. Reference 

unit wiring diagram.

o

  Filters can load up with dirt during building 

construction. Replace any dirty pleated filters and 
clean the aluminum mesh filters in the intake hood 
(refer to Routine Maintenance section).

o

  Verify that non-motorized dampers open and close 

properly.

o

  Check the tightness of all factory wiring connections.

o

  Verify control wire gauge (refer to the Electrical 

Connections section).

General Start-Up Information

Every installation requires a comprehensive start-up 
to ensure proper operation of the unit. As part of that 
process, the following checklist must be completed and 
information recorded. Starting up the unit in accordance 
with this checklist will not only ensure proper operation, 
but will also provide valuable information to personnel 
performing future maintenance. Should an issue arise 
which requires factory assistance, this completed 
document will allow unit experts to provide quicker 
resolve. Qualified personnel should perform start-up to 
ensure safe and proper practices are followed.
Unit Model Number   _______________________________
 

(e.g. ECV-10)

Unit Serial Number   _______________________________
 

(e.g. 04C99999 or 10111000)

Start-Up Date 

 _______________________________

Start-Up Personnel Name __________________________
Start-Up Company   _______________________________
Phone Number 

 _______________________________

DANGER

Electric shock hazard. Can cause injury or death. 
Before attempting to perform any service or 
maintenance, turn the electrical power to unit to OFF 
at disconnect switch(es). Unit may have multiple 
power supplies.

WARNING

Use caution when removing access panels or other 
unit components, especially while standing on a 
ladder or other potentially unsteady base. Access 
panels and unit components can be heavy and 
serious injury may occur.
Do not operate energy core ventilator without the 
filters and birdscreens installed. They prevent the 
entry of foreign objects such as leaves, birds, etc.

CAUTION

Do not run unit during construction phase. Damage to 
internal components may result and void warranty.

SPECIAL TOOLS REQUIRED

•  Voltage Meter (with wire probes)
•  Amperage Meter
• Thermometer
• Tachometer
•  Incline Manometer or Equivalent

Start-Up Checklist

The unit will be in operational mode during start-up. Use 
necessary precautions to avoid injury. All data must be 
collected while the unit is running. In order to measure 
volts & amps, the control center door must be open, 
and the unit energized using a crescent wrench to turn 
the disconnect handle.

Check line voltage at unit disconnect

   _______   L1-L2 volts
   _______   L2-L3 volts
   _______   L1-L3 volts

Motor Amp Draw

    • Supply Fan 

• Exhaust Fan

   _______   L1 amps 

 ______   L1 amps

   _______   L2 amps 

 ______   L2 amps

   _______   L3 amps 

 ______   L3 amps

Fan RPM

   _______   Supply Fan   ______   Exhaust Fan

Correct fan rotation direction

    Supply Fan 

Yes  /  No

    Exhaust Fan 

Yes  /  No

Содержание ECV Series

Страница 1: ...plicable Follow the Canadian Electrical Code CEC in Canada 2 All moving parts must be free to rotate without striking or rubbing any stationary objects 3 Unit must be securely and adequately grounded...

Страница 2: ...contactor in the air handler closes to start the unit Summer Operation Outdoor air is preconditioned temperature and moisture levels are decreased by the transfer of energy from the cooler drier retu...

Страница 3: ...nt condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose t...

Страница 4: ...AIR INTAKE OUTDOOR AIR INTAKE A B C EXHAUST AIR DISCHARGE SUPPLY AIR DISCHARGE NON ELECTRICAL SIDE D G E F Top and Bottom Connections Top and End Connections OUTDOOR AIR INLET A B C EXHAUST AIR DISCH...

Страница 5: ...Discharge End Recommended Minimum Recommended Minimum Weatherhood Yes Weatherhood No Weatherhood Yes Weatherhood No ECV 10 30 20 30 No Access Required 33 No Access Required 24 No Access Required ECV...

Страница 6: ...r replacement and maintenance Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary Lifting WARNING All factory provided li...

Страница 7: ...et the Unit Lift unit to a point directly above the curb and duct openings Guide unit while lowering to align with duct openings Roof curbs fit inside the unit base Make sure the unit is properly seat...

Страница 8: ...52 x 16 6 Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute FPM at minimum airflow and up to 1600 fpm at maximum airflow Recommende...

Страница 9: ...em Voltage Supply See voltage use range on the rating plate Measure and record each supply leg voltage at all line disconnect switches Readings must fall within the allowable range on the rating plate...

Страница 10: ...to switch Dirty filter light Economizer light Frost control light On Off Auto Switch Indictor Light Wiring Typical Control Center Components 1 Main Disconnect nonfusible lockable 2 Motor Starter Exhau...

Страница 11: ...VG reference unit wiring diagram ST2 M1 WHITE T1 T3 SUPPLY FAN MOTOR 15 16 0 10VDC BLACK POT BLACK 2CBL M1 RED RED CLOSED 115 120V OPEN 208 230 277V M2 EXHAUST FAN MOTOR 17 18 0 10VDC POT BLACK RED RE...

Страница 12: ...ature and enable the preheater if required If the temperature falls below the set point the electric preheater will turn on Access to the electric preheat is through the outdoor air filter access door...

Страница 13: ...Unit Serial Number ________________________________ e g 04C99999 or 10111000 Start Up Date ________________________________ Start Up Personnel Name___________________________ Start Up Company ________...

Страница 14: ...thermostat 36 F Differential 2 F Timer Refer to page 17 Economizer Application Operation section Yes No Economizer temperature Set point 65 F Offset 20 F Differential 2 F Yes No Economizer enthalpy S...

Страница 15: ...AUTION When operating conditions of the fan are to be changed speed pressure temperature etc consult Greenheck to determine if the unit can operate safely at the new conditions Direction of Fan Wheel...

Страница 16: ...CHANGE STORED displays 9 Press enter to return the current menu parameter 10 Press escape to return to the current menu parameter When values are displayed pressing and holding the or button causes t...

Страница 17: ...PPM CO2 Variable Frequency Drive The ECV 20 and ECV 30 are wired to the Variable Frequency Drive VFD Refer to the Variable Frequency Drive section for control sequence and programming Timer Scale Time...

Страница 18: ...ctory set points refer to Yaskawa VFD instruction manual which can be found online at www drives com MAMBMC RP H1 SC HC S7 S6 S5 S4 S3 S2 S1 MP AC AM AC V A2 A1 PC P2 P1 IG S S R R V1000 MAMBMC AC AM...

Страница 19: ...er rectangular panel This will allow access to the supply blower that is located on the control side of the housing Replace panel after service reinstall core support that was removed then reinstall c...

Страница 20: ...power to the unit Remove access panel Removing the energy recovery core Once the energy core access doors are removed the core can be pulled from the housing To replace the core reverse the procedure...

Страница 21: ...consult the factory Clearing Alarms Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the...

Страница 22: ...w prior to contacting the factory please determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SM...

Страница 23: ...power too low See specifications and catalog for fan curves to determine if horsepower is sufficient Shorted windings in motor Replace motor Low airflow cfm Unit damper not fully open Adjust damper li...

Страница 24: ...Resources Library Literature Greenheck catalog Energy Core Ventilators Model MiniCore and ECV provides additional information describing the equipment fan performance available accessories and specif...

Отзывы: