background image

Energy Core Ventilator

12

®

Optional Component Overview

Economizer

The energy core operation can be altered to take 
advantage of economizer operation (free cooling). Two 
control options are available:
  1.  Bypass damper
  2.   Exhaust only operation

Bypass damper

: An integral bypass damper will cycle 

into a bypass condition allowing cool air to flow past the 
energy recovery core rather than flow through it. When 
outdoor air conditions are not suitable for economizer 
operation, the damper will remain closed. Economizer 
mode is initiated by temperature or enthalpy and 
dependent on the sensor. To eliminate unnecessary 
control sequences and the concern of overloading fans. 
Energizing the bypass damper is accomplished one of 
two ways:
  1.  The outdoor air temperature is <40ºF or >65ºF.
  2.   The outdoor air temperature is <40ºF or >65ºF DB 

or >55˚F dew point.

Exhaust only operation

: This option allows for the 

exhaust fan to run continuously while the supply fan 
is off. 

Frost Control

Extremely cold outdoor air temperatures can cause 
moisture condensation and frosting on the energy 
recovery core. Timed exhaust and an electric preheater 
are optional frost control features that will prevent/
control core frosting. 

Timed exhaust

 frost control includes a timer as well as 

an adjustable thermostat (preset at 36°F) that is factory 
installed in the exhaust airstream. When timed exhaust 
frost control is initiated, the timer will turn the supply 
blower off. Timed exhaust uses a default timer setting 
that will shut down the supply fan for 5 minutes every 
30 minutes to allow for the exhaust air to defrost the 
energy core. 

Electric preheat 

comes standard as single-stage 

on/off control. Preheaters are single point wired at 
the factory. An adjustable thermostat (preset at 36°F) 
is mounted in the exhaust airstream to monitor the 
discharge air temperature and enable the preheater if 
required. If the temperature falls below the set point, 
the electric preheater will turn on. Access to the electric 
preheat is through the outdoor air filter access door. 
Reference 

Optional Start Up Components, Frost 

Control Test Procedure

 for troubleshooting.

Variable Frequency Drives (VFD)

VFDs are used to control the speed of the fan as either 
multi-speed or modulating control. Multi-speed VFDs 
reference a contact which can be made by a switch or 
a sensor with a satisfied set point. Modulating control 
references a 2-10 VDC signal to the VFD which will vary 
the fan speed from a minimum 50% to full 100% rpm. 
An optional CO

2

 sensor is available to provide both a 

set point contact or a modulating 2-10 VDC signal. 

CO

2

 Sensor

The factory-provided sensors can be set to reference a 
set point for on/off operation.
On model ECV, this accessory is often used in Demand 
Control Ventilation (DCV) applications. The factory 
provided sensor can be set to reference a set point for 
multi-speed operation on the ECV-20 and ECV-30. The 
CO

2

 sensor can also be used to output a 2-10 VDC 

signal to modulate the fan speed on the ECV-10-VG, 
ECV-20 and ECV-30. 
The CO

2

 sensor is either shipped loose to mount in 

the room space, ductwork, or is factory-mounted in 
the return air intake. Follow instructions supplied with 
sensor for installation and wiring details.

Dirty Filter Sensor

Dirty filter sensors monitor pressure drop across the 
outdoor air filters, exhaust air filters, or both. If the 
pressure drop across the filters exceeds the set point, 
the sensor will close a set of contacts in the unit control 
center. Field-wiring of a light (or other alarm) to these 
contacts will notify maintenance personnel when filters 
need to be replaced. The switch has not been set at the 
factory due to external system losses that will affect the 
switch. This switch will need minor field adjustments 
after the unit has been installed with all ductwork 
complete. The dirty filter switch is mounted in the unit 
control center.

Содержание ECV Series

Страница 1: ...plicable Follow the Canadian Electrical Code CEC in Canada 2 All moving parts must be free to rotate without striking or rubbing any stationary objects 3 Unit must be securely and adequately grounded...

Страница 2: ...contactor in the air handler closes to start the unit Summer Operation Outdoor air is preconditioned temperature and moisture levels are decreased by the transfer of energy from the cooler drier retu...

Страница 3: ...nt condensation Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid condensation allow cold parts to reach room temperature Leave coverings loose t...

Страница 4: ...AIR INTAKE OUTDOOR AIR INTAKE A B C EXHAUST AIR DISCHARGE SUPPLY AIR DISCHARGE NON ELECTRICAL SIDE D G E F Top and Bottom Connections Top and End Connections OUTDOOR AIR INLET A B C EXHAUST AIR DISCH...

Страница 5: ...Discharge End Recommended Minimum Recommended Minimum Weatherhood Yes Weatherhood No Weatherhood Yes Weatherhood No ECV 10 30 20 30 No Access Required 33 No Access Required 24 No Access Required ECV...

Страница 6: ...r replacement and maintenance Sufficient space should be provided on the side of the unit for routine service and component removal should that become necessary Lifting WARNING All factory provided li...

Страница 7: ...et the Unit Lift unit to a point directly above the curb and duct openings Guide unit while lowering to align with duct openings Roof curbs fit inside the unit base Make sure the unit is properly seat...

Страница 8: ...52 x 16 6 Recommended duct sizes are based on velocities across the cfm range of each model at approximately 800 feet per minute FPM at minimum airflow and up to 1600 fpm at maximum airflow Recommende...

Страница 9: ...em Voltage Supply See voltage use range on the rating plate Measure and record each supply leg voltage at all line disconnect switches Readings must fall within the allowable range on the rating plate...

Страница 10: ...to switch Dirty filter light Economizer light Frost control light On Off Auto Switch Indictor Light Wiring Typical Control Center Components 1 Main Disconnect nonfusible lockable 2 Motor Starter Exhau...

Страница 11: ...VG reference unit wiring diagram ST2 M1 WHITE T1 T3 SUPPLY FAN MOTOR 15 16 0 10VDC BLACK POT BLACK 2CBL M1 RED RED CLOSED 115 120V OPEN 208 230 277V M2 EXHAUST FAN MOTOR 17 18 0 10VDC POT BLACK RED RE...

Страница 12: ...ature and enable the preheater if required If the temperature falls below the set point the electric preheater will turn on Access to the electric preheat is through the outdoor air filter access door...

Страница 13: ...Unit Serial Number ________________________________ e g 04C99999 or 10111000 Start Up Date ________________________________ Start Up Personnel Name___________________________ Start Up Company ________...

Страница 14: ...thermostat 36 F Differential 2 F Timer Refer to page 17 Economizer Application Operation section Yes No Economizer temperature Set point 65 F Offset 20 F Differential 2 F Yes No Economizer enthalpy S...

Страница 15: ...AUTION When operating conditions of the fan are to be changed speed pressure temperature etc consult Greenheck to determine if the unit can operate safely at the new conditions Direction of Fan Wheel...

Страница 16: ...CHANGE STORED displays 9 Press enter to return the current menu parameter 10 Press escape to return to the current menu parameter When values are displayed pressing and holding the or button causes t...

Страница 17: ...PPM CO2 Variable Frequency Drive The ECV 20 and ECV 30 are wired to the Variable Frequency Drive VFD Refer to the Variable Frequency Drive section for control sequence and programming Timer Scale Time...

Страница 18: ...ctory set points refer to Yaskawa VFD instruction manual which can be found online at www drives com MAMBMC RP H1 SC HC S7 S6 S5 S4 S3 S2 S1 MP AC AM AC V A2 A1 PC P2 P1 IG S S R R V1000 MAMBMC AC AM...

Страница 19: ...er rectangular panel This will allow access to the supply blower that is located on the control side of the housing Replace panel after service reinstall core support that was removed then reinstall c...

Страница 20: ...power to the unit Remove access panel Removing the energy recovery core Once the energy core access doors are removed the core can be pulled from the housing To replace the core reverse the procedure...

Страница 21: ...consult the factory Clearing Alarms Once the alarm has been identified and the cause has been removed e g replaced faulty sensor the alarm can be cleared from the display To clear an alarm perform the...

Страница 22: ...w prior to contacting the factory please determine the following information Airflow problems can often be tied back to improper ductwork installation Be sure to install ductwork in accordance with SM...

Страница 23: ...power too low See specifications and catalog for fan curves to determine if horsepower is sufficient Shorted windings in motor Replace motor Low airflow cfm Unit damper not fully open Adjust damper li...

Страница 24: ...Resources Library Literature Greenheck catalog Energy Core Ventilators Model MiniCore and ECV provides additional information describing the equipment fan performance available accessories and specif...

Отзывы: